Power Requirements
•
24 VAC (dedicated transformer) or +12 VDC @ 0.25A (supplied by the ADM-2W704)
•
40 VA
•
Class II
Ambient Ratings
•
32º to 131º F (0º to 55º C)
•
10 to 90% RH (non-condensing)
Communication Ports
NET1 - Main LAN (MS/TP)
•
Communications Speed @ 9,600, 19,200, 38,400 or 76,800 bps
•
Maximum of 99 nodes per MS/TP segment
•
Visual LED status of network activity
NET2 - Sub LAN (LINKnet or MS/TP)
•
Communications Speed @ 9,600, 19,200, 38,400 or 76,800 bps
•
For Linknet: Maximum of 12 Access Door Modules per Access System Manager (ASM-24)
•
For MS/TP: Maximum of 99 nodes per MS/TP segment
•
Visual LED status of network activity
Ethernet (ASM-24E only)
•
10 Base-T
•
Visual LED Status of network activity
Serial Port (RS232)
•
Communications Speed @ 9,600, 19,200 or 38,400 bps
•
Point-To-Point, EIA 232 (Clause 10)
Inputs
•
None
Outputs
•
None
Technology
•
16-bit Processor
•
1 MB (8 Mb) Flash Memory
•
512 KB SRAM memory
•
Real-time Clock with Lithium Battery for Clock & SRAM backup
•
Visual LED status indication of CPU and SCAN Status
Device Addressing
•
Set via DIP switch and jumpers, or Software Setup
•
DIP switch Address Range: 1 to 99 per network segment
•
Software Address Range: As per the BACnet standard
•
Supports DNA – Delta’s intuitive addressing scheme