Expert
Logger
1. Open the "Create network configuration" menu in DataService Con-
figurator.
l
Open the channel overview in DataService Configurator.
l
Click a device with the right mouse button.
l
Select the menu item
Create network configuration
(only available for devices with
Meti
OS
: devices of the
Expert
series as well as
Profi
Message
).
2. Modify the corresponding input fields:
l
Serial number
: Enter the serial number of the device on which you want to change the net-
work settings.
l
Select the desired settings for DHCP, IP address, net mask, gateway and MTU.
3. Now select the storage location of the configuration with
Save as
.
4. Confirm the dialogue by pressing "OK".
5. Save the file to the main directory of a USB memory stick formatted with
FAT16 or FAT32.
6. Plug the USB memory stick in to the device.
7. After a few seconds, the network configuration should have changed.
Info
You can download an XML template for network configuration on the
website of a device. To do this, click the "XML template network config
file" link on the device website or visit the "<Device IP>/doc/Network-
SN00000000.xml" link.
Also visit the
XML Template for Network Configuration
Help Centre.
4.9 System channels
This Section explains the settings for the System group. The settings for
drives available only for expert devices can be found in
.
4.9.1
Time and clock settings
In this group, some channels are already set by default, which are relevant
to the time and date settings:
l
software channel setting)
l
Clock frequency error, Stratum (synchronisation chain) or Sync (syn-
chronisation available) are
software channel settings
l
Time (zone) and clock (synchronisation) settings (the channel is also avail-
able as a copy in
Synchronisation via NTP
The NPT time (Network Time Protocol) is a number that contains the num-
ber of seconds that have passed since midnight (00:00 h) on 1 January
1970, with a resolution greater than one microsecond. The NPT time refers
to GMT (Greenwich Mean Time).
Further information is available from
and
.
60
Delphin Technology AG
Januar 2018
Expert
Logger
Manual