BRAN H
(1) Heat pump mode: External air temperature 7°C DB- 6°C WB, water in flow at 30°C and out flow at 35°C
(2) The total input is given by the compressor input + fans power input
(3) Noise level measured in free field at a distance of 1 metre
BRAN H
0011M
0025M
0041M
Heating capacity (1)
kW
6,5
8,7
13,8
Effective input power according to EN 14511 (1)
kW
1,82
2,31
3,68
COP according to EN 14511 (1)
3,57
3,76
3,75
Heating capacity (1)
kW
6,5
8,7
13,8
Power absorbed (2)
kW
1,65
2,15
3,40
COP (2)
3,94
4,05
4,06
Rated water flow (1)
m
3
/h
1,12
1,50
2,37
Residual head (1)
kPa
41
48
89
Fans
n°
1
1
2
Air Flow
m
3
/s
0,9
1
1,9
Type of compressor
SCROLL
No. of compressors
n°
1
1
1
No. of circuits
n°
1
1
1
Refrigerant R410A
Kg
1,75
3
3
Oil Mobil EAL ARTIC 22cc
Kg
1,1
1,24
1,95
Pump type
Circulator
No. of pumps
n°
1
1
1
Functioning weight
kg
95
115
140
Hydraulic connections
inches
3/4
3/4
1 1/4
Sound power level according to EN ISO 3744
dB(A)
72
73
73
Sound pressure (3)
dB(A)
61
62
62
Electric power supply
V/ph/Hz
230~50
GENERAL TECHNICAL DATA
I A