Installation Guide
13
To install a PDU horizontally in the 1-U space at the back of your rack, perform the following steps:
1
Open the front and back doors of the rack cabinet.
2
Identify and mark the location for the PDU in the lowest single-unit (1 U) position in which it
can be installed or in the position that is closest to the systems to which it will supply power.
Ensure that all power cords that you intend to connect to the PDU can reach the PDU location
you have selected.
3
Remove the 0-U mounting bracket from the PDU case by removing the six 6-32 x 0.31-inch flat-head
screws at the ends of the PDU case.
Save these screws to use in attaching the 1-U mounting brackets in step 4 (see Figure 1-5).
Figure 1-5.
Removing the 0-U Mounting Bracket
4
Secure the two 1-U mounting brackets to the PDU case with the screws you removed in step 3
making a tight connection (torque value is approximately 6-8 in-lbs), as shown in Figure 1-6.
5
Install the cage nuts in the second holes of the selected 1-U position on the rails.
6
Position the PDU and secure the unit to the rails with screws and washers, making a tight connection
(torque value is approximately 12-16 in-lbs), as shown in Figure 1-6.
0-U mounting bracket
PDU case
6-32 x 0.31-inch
flat-head
screws (6)
Summary of Contents for RapidPower 10-A IEC power strip
Page 2: ......
Page 6: ...4 Contents ...
Page 26: ...24 Installation Guide ...
Page 28: ...26 Index 26 Index ...
Page 32: ...30 Sommaire ...
Page 54: ...52 Guide d installation ...
Page 56: ...54 Index 54 Index ...
Page 60: ...58 Inhalt ...
Page 82: ...80 Installationsanleitung ...
Page 84: ...82 Index 82 Index ...
Page 85: ...w w w d e l l c o m s u p p o r t d e l l c o m Dell RapidPower 配電ユニット 取り付けガイド ...
Page 88: ...86 目次 ...
Page 95: ...取り付けガイド 93 図 1 3 PDU システムの 0 U 取り付け位置 水平レール 2 背面垂直レール 2 水平レール用スペーサパッド 前面 出力コネクタ用レールの切り欠き ...
Page 110: ...108 索引 108 索引 ...
Page 114: ...112 Contenido ...
Page 138: ...136 Índice 136 Índice ...