Type
Condition
Temperature or Specification
Storage
Six consecutively executed shock pulses in the positive and
negative x, y, and z axes (one pulse on each side of the
system) of 105 G for up to 2 ms.
Maximum Altitude
Operating
3,048 m (10,000 ft)
Storage
35,000 m (10,688 ft)
Operating Altitude De-rating
Up to 35 °C (95 °F)
Maximum temperature is reduced by 1 °C/300 m (1 °F/547
ft) above 950 m (3,117 ft).
35 °C to 40 °C (95 °F to 104 °F)
Maximum temperature is reduced by 1 °C/175 m (1 °F/319
ft) above 950 m (3,117 ft).
40 °C to 45 °C (104 °F to 113 °F)
Maximum temperature is reduced by 1 °C/125 m (1 °F/228
ft) above 950 m (3,117 ft).
Particulate and gaseous contamination specifications
The following table defines the limitations that help avoid any equipment damage or failure from particulates and gaseous contamination. If
the levels of particulates or gaseous pollution exceed the specified limitations and result in equipment damage or failure, you may need to
rectify the environmental conditions. Re-mediation of environmental conditions is the responsibility of the customer.
NOTE:
This section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous
contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits specified in the following
table and are the reason for the damage and/or failures to your equipment, it may be necessary for you to re-mediate the
environmental conditions that are causing the damage and/or failures. Re-mediation of environmental conditions will be the
responsibility of the customer.
Table 18. Particulate contamination specifications
Particulate contamination
Specifications
Air Filtration
NOTE:
Applies to data center environments only. Air filtration
requirements do not apply to IT equipment designed to be used
outside a data center, in environments such as an office or
factory floor.
Data center air filtration as defined by ISO Class 8 per ISO
14644-1 with a 95% upper confidence limit.
NOTE:
Air entering the data center must have
MERV11 or MERV13 filtration.
Conductive Dust
NOTE:
Applies to data center and non-data center
environments.
Air must be free of conductive dust, zinc whiskers, or other
conductive particles.
Corrosive Dust
NOTE:
Applies to data center and non-data center
environments.
•
Air must be free of corrosive dust.
•
Residual dust present in the air must have a deliquescent
point less than 60% relative humidity.
Table 19. Gaseous contamination specifications
Gaseous contamination
Specifications
Copper Coupon Corrosion Rate
<300 Å/month per Class G1 as defined by ANSI/ISA71.04-1985.