Dell PowerConnect W-6000 Installation Manual Download Page 4

4

Dell PowerConnect W-6000 Power Supply

| Installation Guide

3. Verify the power switch on the power supply to be installed is Off (

).

4. Insert the power supply into the chassis.

Grasp the power supply by the handle attached along the bottom side of the power supply, keeping the LEDs 
on the left and power switch on the right. Do not use the power cord retaining clip to insert or remove the 
power supply. Align the back of the module with the guide-rails in the chassis power supply slot and gently 
slide the module toward the backplane. Do not force the module; it should slide in easily most of the way. 
There may be moderate resistance when the power supply meets the connectors at the back of the chassis. 
Press firmly to engage the connectors, but do not use excessive force.

5. Secure the power supply.

Use the screwdriver to push in the module’s captive fastening screws and turn them clockwise until moderate 
resistance is felt. Do not over-tighten.

6. Attach the power cord to the power supply.

Plug an appropriate power cord into the power input socket. The socket accepts a power cord with a standard 
IEC320 plug.

7. Secure the power cord.

When the power cord is attached, swing the power cord retaining clip to the right as shown in 

Figure 3 on 

page 4

. This will hold the plug in place and help prevent it from being removed accidentally.

Figure 3  

Using the Power Cord Retaining Clip

8. Attach the power cord to a proper electrical outlet.

Verify that your site’s electrical systems can handle the power load.

Each power supply (HW-PSU-400) is rated at 400 W total and is auto-ranging to accept 85 to 264 VAC, at 
50 to 60 Hz.

CAUTION:  Never insert or remove a power supply while its power switch is in the On (

|

) position or if the power cord is plugged 

into the power supply module. Verify the power switch is Off (

) first and that the power cord is unplugged from the W-6000 PSU 

module.

NOTE:  Swing the cord retaining clip to the left before attaching the power cord.

CAUTION:  For proper safety and performance, the power cord must be rated to 10 A and conform to grounded electrical 
standards in the country where the product is operated.

Right: Capture Cord

Wrong: Around Plug Base

Summary of Contents for PowerConnect W-6000

Page 1: ...urned on Load sharing divides the total power load of the W 6000 among all plugged in power supply modules Since the power supplies work together the effective power capacity of the chassis is increased with each additional power supply Redundancy When multiple power supplies are installed if one becomes unavailable fails or is turned off or removed the remaining power supplies will attempt to pro...

Page 2: ...ket accepts power cords with standard IEC320 connectors For proper safety and performance the cord must be rated to 10 A and conform to grounded electrical standards in the country where the product is used O T P DC OK AC OK 1 7 6 5 4 1 2 3 6 5A MAX 1 2 CAUTION Do not use the power supply handle to lift or move the W 6000 Serious damage could result Table 1 400W Power Supply LEDs LED Name Position...

Page 3: ...led in any power supply slot and any power supply slot can be left empty That is there is no specific required order of slots used for power supplies Figure 2 400 W Power Supplies Installed If replacing a previously installed power supply first see Removing a Power Supply on page 5 If you are installing a power supply in an empty slot you may have to remove the blank cover plate first To do this u...

Page 4: ...wer supply Plug an appropriate power cord into the power input socket The socket accepts a power cord with a standard IEC320 plug 7 Secure the power cord When the power cord is attached swing the power cord retaining clip to the right as shown in Figure 3 on page 4 This will hold the plug in place and help prevent it from being removed accidentally Figure 3 Using the Power Cord Retaining Clip 8 At...

Page 5: ...ull the module out of the chassis 5 Cover blank slots For safety considerations as well as to promote proper air flow for cooling and to prevent dust from entering the chassis cover any unoccupied slot with a blank cover plate CAUTION For safety reasons verify the power outlets and plugs are within easy reach of the operator and can be quickly disconnected if necessary NOTE Use of a power line con...

Page 6: ...GPL or other Open Source Licenses The Open Source code used can be found at this site http www arubanetworks com open_source Legal Notice The use of Aruba Networks Inc switching platforms and software by all individuals or corporations to terminate other vendors VPN client devices constitutes complete acceptance of liability by that individual or corporation for this action and indemnifies in full...