45
Operation
|
Table 7. Settings (continued)
Description
Default Setting
Available Settings
Synchronization Window
[Sync Disabled] [
±
0.5 Hz] [
±
1.0 Hz] [
±
1.5 Hz]
[
±
2.0 Hz] [
±
2.5 Hz] [
±
3.0 Hz]
If
±
3.0 Hz, on inverter operation the inverter tries to
synchronize with the Bypass when the Bypass
frequency is not more than 3 Hz from the nominal
output frequency; otherwise, the inverter goes to
nominal frequency. On Bypass mode, the sync
window is always
±
3 Hz.
NOTE:
In Sync Disabled state, if the Bypass
operation is allowed, the UPS synchronizes only
when it is operating on Bypass mode.
±
3.0 Hz
Unsynchronized Transfers
[Enabled] [Disabled]
If Enabled, unsynchronized transfers to the Bypass
are allowed.
If Disabled, unsynchronized transfers to the Bypass
are not allowed.
NOTE:
The Qualify Bypass setting may overrule the
Unsynchronized Transfers setting.
Enabled
External Battery Modules (EBMs)
[0] [1]
See “Configuring the UPS for an EBM” on page 52.
0
Charger
[Enabled] [Disabled]
If Enabled, batteries charge normally.
If Disabled, the battery charger is off.
Enabled
Battery Charge % to Restart
[0%] [10%] [20%] [30%]...[100%]
When enabled, automatic restart is made when the
battery charge state reaches the selected level. If set
to 0%, the feature is disabled.
0%
Battery Low Alarm
[Immediate] [2 min] [3 min] [5 min]
If you select a value, the battery low alarm triggers
when the set amount of backup time
(approximately) remains in the batteries.
3 min
Automatic Battery Tests
[Enabled] [Disabled]
See “Running Automatic Battery Tests” on page 53.
Enabled