A
SPS Technical Specifications
A-9
Technical Specifications and Operating Limits
Operating Limits
IMPORTANT:
The operating limits listed above for temperature and
humidity must not be exceeded inside the closed cabinet in which the SPS is
mounted. For proper ventilation, airflow must not be restricted along the
sides of the SPS.
Non-Operating
Limits (Shipping and
Storing)
Dimensions and
Battery Information
Dimensions
Service Clearance
Ambient temperature
10°C to 40°C (50°F to 104°F)
Relative humidity
20% to 80% noncondensing
Elevation
2439 m (8000 ft)
Ambient temperature
-40°C to 65°C (-40°F to 149°F)
Gradient, maximum
24°C/hr (75°F/hr)
Relative humidity
10% to 90% noncondensing
Elevation
7625 m (25,000 ft)
Height
4.02 cm (1.58 in)
Width
20.1 cm (8.25 in)
Length
53.9 cm (21.2 in)
Weight
9.1 kg (20 lb)
Front
81.3 cm (32.0 in)
Rear
81.3 cm (32.0 in)
Summary of Contents for IP4700
Page 4: ...IP4700 Installation and Service Guide iv ...
Page 8: ...IP4700 Installation and Service Guide viii Contents ...
Page 12: ...xii IP4700 Installation and Service Guide Preface ...
Page 18: ...xviii IP4700 Installation and Service Guide Warnings and Cautions ...
Page 60: ...2 2 24 IP4700 Installation and Service Guide Installing an IP4700 ...