Dell 3750W Site Preparation Manual Download Page 3

Dell UPS Site Preparation Guide, EMEA (230V) 

 

Revision 1, February 2012 

Electrical Preparation: 

Electrical Requirements for the Dell UPS

 

UPS Model 

UPS Technology 

Input Voltage (VAC) 

Power Draw 

(standby) 

 

Overcurrent 

Protection 

Minimum Wire Size 

(LiveNeutral/Ground) 

3750W Rack 

Online 

208, 220, 230, 240 

186W 

 

25A 1-phase 

10 / 10 AWG 

4200W Rack 

Online 

208, 220, 230, 240 

210W 

 

30A 1-phase 

10 / 10 AWG 

5600W Rack 

Line-Interactive 

208, 220, 230, 240 

224W 

 

32A 1-phase 

10 / 10 AWG 

5600W Rack 

Online 

208, 220, 230, 240 

143W 

 

32A 1-phase 

8 / 10 AWG 

 
Note:

  

Overcurrent protection should be ‘slow-break’, suitable for devices with a high inrush current.  Normally this should be a fuse or 

circuit breaker with a Type-C or Type-3 rating.

 

 

Electrical Requirements for the REPO Switch (Remote Emergency Power Off) 

REPO is used to shut down the UPS from a distance. For example, this feature can be used for shutting down the 
load and the UPS by thermal relay, in the event of room over-temperature. When REPO is activated, the UPS shuts 
down the output and all its power converters immediately. The UPS logic power remains on to issue an alarm. 

The REPO feature shuts down the protected equipment immediately and does not follow the orderly shutdown 
procedure initiated by any power management software. Any devices that are operating on battery power are also 
shut down immediately. When the REPO switch is reset, the equipment will not return to utility or battery power 
until the UPS is manually restarted. 

There are two REPO ports on each UPS in order to support cascaded REPO functionality.  This allows a single cable to 
be cascaded between multiple Dell UPS, eliminating the need for a dedicated REPO cable for each UPS & simplifying 
installation. 

The REPO contacts are normally open. 

Wire Function 

Terminal Wire Size Rating 

Suggested Wire Size  

Remote Emergency Power Off (REPO) 

4-0.32mm

2

 (12-22 AWG) 

0.82mm

2

 (18 AWG) 

 

WARNING:

 The REPO circuit is an IEC 60950 safety extra low voltage (SELV) circuit. This circuit must be separated from any 

hazardous voltage circuits by reinforced insulation. 

 
CAUTION:

 The REPO must not be connected to any utility connected circuits. Reinforced insulation to the utility is required. The 

REPO switch must have a minimum rating of 24Vdc and 20 mA and be a dedicated latching-type switch not tied into any other 
circuit. The REPO signal must remain active for at least 250ms for proper operation. 

 
NOTE:

 For Europe, the emergency switch requirements are detailed in Harmonized document HD-384-48 S1, “Electrical 

Installation of the Buildings, Part 4: Protection for Safety, Chapter 46: Isolation and Switching.”  

NOTE: 

The pins must be open to keep the UPS running. If the UPS shuts down because the REPO connector pins are shorted, 

restart the UPS by re-opening the REPO connector pins and turning on the UPS manually. 

Maximum resistance in the shorted loop is 10 ohm. 

NOTE:

 Always test the REPO function before applying your critical load to avoid accidental load loss. 

 

 

Summary of Contents for 3750W

Page 1: ...autions are included within the UPS User Guide Site Preparation Checklist Installation site meets minimum environmental requirements Ensured all required accessories have been ordered with the UPS Electrical Preparation Required electrical supply is available Scheduled an electrician to install the Dell UPS Provided a copy of this preparation guide to the electrician Made electrician aware of the ...

Page 2: ...condensing Elevation Operation 0 3048m 0 10 000ft Elevation Storage 0 15 340m 0 50 000ft Heat Output for the Dell UPS UPS Model UPS Technology Heat Loss Watts BTU normal mode Heat Loss Watts BTU battery mode 3750W Rack Online 188 640 375 1281 4200W Rack Online 210 717 420 1434 5600W Rack Line Interactive 280 956 560 1921 5600W Rack Online 390 989 420 1433 Optional accessories for Dell UPS Optional...

Page 3: ...equipment will not return to utility or battery power until the UPS is manually restarted There are two REPO ports on each UPS in order to support cascaded REPO functionality This allows a single cable to be cascaded between multiple Dell UPS eliminating the need for a dedicated REPO cable for each UPS simplifying installation The REPO contacts are normally open Wire Function Terminal Wire Size Ra...

Page 4: ...ring Basic Installation Schematics Basic Installation Schematic of Dell UPS using optional power input cord Suitable for all models except 5600W Online Basic Installation Schematic of Dell UPS hardwired to overcurrent protection device Suitable for all models including 5600W Online ...

Page 5: ...rrent backfeed Dell recommends installing an external isolating device see illustration below After the device is installed you must add a warning label with the following wording or the equivalent on the external AC contactor RISK OF VOLTAGE BACKFEED Isolate the UPS before operating on this circuit then check for hazardous voltage between all terminals The following table lists AC contactors that...

Page 6: ...e the back side nearest cable bare ends of the plastic stuffing gland from the input cord kit Step 3 Thread the input cord through the UPS back plate and secure with the plastic stuffing gland Ensure you leave enough free cord to connect to the UPS terminals Step 4 Secure the bare cable ends to the UPS terminals replace the cover plate Wire Colour Terminal Position UPS Wire Function Terminal Wire ...

Page 7: ...r guide or visit www dellups com Configure UPS List All UPS Your model Note that for some Dell UPS models the rack mount rails may be packed below the UPS in the box CAUTION Refer to the user guide for complete instructions including important Health Safety advice CAUTION This equipment is heavy refer to the user guide for advice on unpacking and safe installation Installing the Dell UPS into the ...

Page 8: ...Dell UPS Site Preparation Guide EMEA 230V Revision 1 February 2012 ...

Reviews: