Hardware acclimation times
Systems and components must acclimate to the operating environment before
applying power. This requires the unpackaged system or component to reside in the
operating environment for up to 16 hours in order to thermally stabilize and prevent
condensation.
on page 123 helps you determine the precise amount of stabilization time
required.
Table 11 Hardware acclimation times (systems and components)
If the last 24 hours of the
TRANSIT/STORAGE
environment was this:
…and the OPERATING
environment is this:
…then let the system
or component
acclimate in the new
environment this many
hours:
Temperature
Humidity
Nominal 68-72°F
(20-22°C)
Nominal
40-55% RH
Nominal 68-72°F (20-22°C)
40-55% RH
0-1 hour
Cold <68°F
(20°C)
Dry <30%
RH
<86°F (30°C)
4 hours
Cold <68°F
(20°C)
Damp ≥30%
RH
<86°F (30°C)
4 hours
Hot >72°F
(22°C)
Dry <30%
RH
<86°F (30°C)
4 hours
Hot >72°F
(22°C)
Humid
30-45% RH
<86°F (30°C)
4 hours
Humid
45-60% RH
<86°F (30°C)
8 hours
Humid
≥60% RH
<86°F (30°C)
16 hours
Unknown
<86°F (30°C)
16 hours
Safety precautions for handling replaceable units
Hardware acclimation times
123