Figure 19. S5296F-ON installation
1
Extra screws to restrict front-back movement of the switch.
2
Main screw
Ground cable
NOTE:
For AC-powered switches, although the third conductor of the AC power cord provides a ground path, Dell EMC
recommends grounding your switch with a dedicated ground wire.
NOTE:
For a DC-powered switch, the only way to safely ground your switch is to attach a dedicated ground wire. The ground lug
kit ships in a plastic bag placed with the other accessories inside the shipping box. The ground lug bracket screws ship attached
to the switch. Before you install the DC switch in the dual-tray, attach the ground lug and bracket to the switch using the
included screws and then attach the DC ground wire to the ground lug.
To attach a ground cable to the switch, use one of the two pre-installed screws.
The ground cable is not included. To properly ground the switch, Dell EMC recommends a one- or two-hole lug, M3 hole size. The ground
lugs must be a UL-recognized, crimp-type lug.
CAUTION:
Grounding conductors
must
be made of copper. Do not use aluminum conductors.
NOTE:
Coat the one-hole lug with an anti-oxidant compound before crimping. Also, bring any unplated mating surfaces to a shiny
finish and coat with an anti-oxidant before mating. Plated mating surfaces must be clean and free from contamination.
S5200F-ON Series switch installation