Parameter
Specifications
S5248F-ON: 21.4 lbs (9.7 kg)—PSUs and fans
S5296F-ON: 33.3 lbs (15.1 kg)—PSUs and fans
Rack clearance required
Front: 5 inches (12.7 cm)
Back: 5 inches (12.7 cm)
Table 8. Environmental parameters
Parameter
Specifications
Operating temperature
0° to 45°C (32°F to 113°F) continuously
NOTE:
Reduce maximum temperature by 1°C/125 meters
(1°F/228 feet) above 950 meters (3,117 feet).
Operating humidity
5% to 90% (RH), non-condensing
Storage temperature
–40° to 70°C (–40° to 158°F )
Storage humidity
5% to 90%, non-condensing
Maximum thermal output
S5232F-ON: 635W = 2167 BTU/Hr
S5248F-ON: 602W = 2054 BTU/Hr
S5296F-ON: 835W = 2849 BTU/Hr
Maximum operational altitude
10,000 feet (3,048 meters)
Maximum non-operational altitude
35,000 feet (10,668 meters)
Shock
Dell EMC Spec SV0115
Table 9. AC power requirements
Parameter
Specifications
Power supply
S5232F-ON: 100–240 VAC 50/60 Hz
S5248F-ON: 100–240 VAC 50/60 Hz
S5296F-ON: 100–240 VAC 50/60 Hz
Maximum current draw per system
S5232F-ON: 7A@110VAC and 3.5A@220VAC
S5248F-ON: 7A@110VAC and 3.5A@220VAC
S5296F-ON: 10A@110VAC and 5A@220VAC
Maximum power consumption
S5232F-ON: 684W maximum
S5248F-ON: 641W maximum
S5296F-ON: 894W maximum
Typical power consumption
S5232F-ON: 479W typical
Specifications