Introduction and Preparation
Topics:
•
•
•
•
Document purpose
This installation guide provides instructions for installing the hardware associated with PowerProtect systems. Systems are
shipped to the customer site either pre-installed in a rack (factory-racked) or as separate components to install in an existing
rack at the site (field-installed). This guide provides instructions for both types of installation.
This document is intended for customers or Dell EMC Support personnel who are qualified to install PowerProtect systems.
Field-installed systems
To install PowerProtect systems in an existing rack at the customer site, follow all the instructions in this document to rack,
cable, and configure the system.
Factory-racked systems
Factory-racked systems are pre-installed in the rack with the cables already connected. Follow the instructions in
on page 64 to configure factory-racked systems.
The following documents, available from the
, provide additional information about factory-racked
systems:
●
Dell EMC 40U-P Cabinet Site Preparation Guide
●
Dell EMC 40U-P Cabinet Unpacking and Setup Guide
●
Dell EMC Titan S Site Preparation Guide
●
Dell EMC Titan S Unpacking and Setup Guide
●
Dell EMC Data Domain Rack Service Guide
Tools and supplies needed
These tools and supplies may be helpful for the installation and setup tasks for Data Domain systems.
●
Null modem cable (DB-9 female to female), plus spare
●
USB-to-DB-9 serial (male connector) converter cable if the laptop does not have a serial port, plus spare
●
Power adapter, C13 to NEMA 5–15 (if based in North America), or a power cord for your laptop power adapter with a C13
plug, so that you can power your laptop from a rack PDU
●
Antistatic wrist strap and conductive foam pad
●
Screwdrivers:
○
Phillips #2 with a 12 in. or longer blade
○
Phillips #2 (standard-length blade)
○
Phillips #1
○
Flat head 3/16 in.
○
Flat head 1/4 in.