38
iTR326A operation
operation display
The ETU needs to display various operation parameters, setting parameters and other values on the
panel
Use LED digital tube to display the value, and use LED indicator to indicate the type of value displayed
ammeter maximum current display
By default, the intelligent controller enters the maximum current display mode of the ammeter to
display the maximum phase current
When the operation display is not the maximum current display mode, there is no key operation within
10 minutes, and the maximum current display mode will be returned automatically
Indicates that the displayed data unit is A
Indicates that the displayed data unit is kA
iTR326A Ammeter maximum current display mode and ammeter display mode display
No.
display
LED indicator
remarks
1
L1
Phase current
LED_L1、LED_A/LED_kA
2
L2
Phase current
LED_L2、LED_A/LED_kA
3
L3
Phase current
LED_L3、LED_A/LED_kA
4
N
Phase current
LED_N、LED_A/LED_kA
LED_ N flash (4P or 3P+N only)
5
Maximum
current
L1
Phase
LED_L1、LED_MAX、LED_A/LED_kA
L2
Phase
LED_L2、LED_MAX、LED_A/LED_kA
L3
Phase
LED_L3、LED_MAX、LED_A/LED_kA
6
Earth current
LED_N、LED_A/LED_kA
LED_ N always on
ammeter display mode
Under normal operation mode, browse the current value and breaker status through the current
selection key
, and the display sequence is breaker status, L1, L2, L3, n-phase current (LED_ N
flashing (4P only), ground current, maximum phase current.
Without any key operation within 10 minutes, it will automatically return to the maximum current
display mode
Breaker opening status
Closing state of circuit breaker Display L1 phase current
parameter setting and display mode
Parameters (user parameters) that users can set on site can be realized through key operation and LED
digital tube and indicator light display
setting and display of protection parameters
The protection parameters can be set by the user on site. The parameter setting is realized by four
buttons (i.e.
,
,
,
). The main operation steps are as follows:
Debugging CDW3