Deka unigy I Installation And Operating Instructions Manual Download Page 1

1

SAFETY PRECAUTIONS

     

VRLA (Valve Regulated Lead-Acid)

batteries have the

electrolyte immobilized within the battery; however, elec-

trical hazard associated with batteries still exists. 

Work

performed on these batteries should be done with

the tools and the protective equipment listed below.

VRLA battery installations should be supervised by per-

sonnel familiar with batteries and battery safety

precautions.

     

WARNING: Risk of fire, explosion or burns. Do not

disassemble, heat above 40°C, or incinerate

.

Protective Equipment

     Although VRLA batteries can vent or leak small amounts

of electrolyte, electrical safety is the principal but not the

only concern for safe handling. Per IEEE 1188 recom-

mendations, the following minimum set of equipment for

safe handling of the battery and protection of personnel

shall be available:

1.   

Safety glasses with side shields, or goggles, or face

shields as appropriate. (Consult application specific

requirements)

2.   Electrically insulated gloves, appropriate for the installation.

3.   Protective aprons and safety shoes.

4.   Portable or stationary water facilities in the battery vicinity for

rinsing eyes and skin in case of contact with acid electrolyte.

5.   Class C fire extinguisher.

6.   Acid neutralizing agent.

7.   Adequately insulated tools. (as defined by IEEE 1188)

8.   Lifting devices of adequate capacity, when required.

®

STATIONARY BATTERY INSTALLATION 

AND OPERATING INSTRUCTIONS

IN REFERENCE TO THIS MANUAL:

– “Battery” is defined as an individual 12-volt unit.
– “Battery string” is defined as a series connected

electrical system comprised of batteries
(individual 12-volt units).

Summary of Contents for unigy I

Page 1: ...tions the following minimum set of equipment for safe handling of the battery and protection of personnel shall be available 1 Safety glasses with side shields or goggles or face shields as appropriate Consult application specific requirements 2 Electrically insulated gloves appropriate for the installation 3 Protective aprons and safety shoes 4 Portable or stationary water facilities in the batte...

Page 2: ...nded Practice for Installation Design of VRLA Batteries IEEE 1188 Recommended Practice for Maintenance Testing of VRLA Batteries IEEE 1189 Selection of VRLA Batteries for Stationary Applications RECEIVING STORAGE Receiving Inspection Upon receipt and at the time of actual unloading each package should be visually inspected for any possible damage or electrolyte leakage If either is evident a more ...

Page 3: ...ell as User Manual of specific application Terminals Upright Position Terminals Upright Front Position Cabinets Cabinet systems come factory assembled and prewired Do not tip or turn cabinets on their sides when position ing them in their intended installation area Cabinets must be used in an upright position These systems are preconnected Only inter shelf inter cabinet and con nections to the loa...

Page 4: ...tteries should be numbered in electrical connection sequence beginning with number one 1 at the positive end of the battery string 3 The interbattery connector contact surfaces shall be cleaned by rubbing gently with a non metallic brush or pad before installing connectors Only approved oxide inhibitors may be applied to connectors or battery posts 1 4 Install all interbattery connectors using loc...

Page 5: ... value re torque the connection con sult Torque Retorque Values Pg 4 Table 1 for proper torque values If reading remains high clean contact sur faces according to Step 2 under Battery Assembly Failure to maintain proper records including information as detailed above may result in voiding any applicable warranty MAINTENANCE Always wear eye protection when working on or near bat teries Keep sparks ...

Page 6: ...5 13 57 84 2 28 13 46 13 58 82 4 27 13 48 13 60 80 6 26 13 49 13 61 78 8 25 13 50 13 62 77 0 24 13 51 13 63 75 2 23 13 52 13 64 73 4 22 13 54 13 66 71 6 21 13 55 13 67 69 8 20 13 56 13 68 68 0 19 13 57 13 69 66 2 18 13 58 13 70 64 4 17 13 60 13 72 62 6 16 13 61 13 73 60 8 15 13 62 13 74 59 0 14 13 63 13 75 57 2 13 13 64 13 76 55 4 12 13 66 13 78 53 6 11 13 67 13 79 51 8 10 13 68 13 80 50 12mV per ...

Page 7: ...0 17 9 5 4 12AVR100ET 17 6 5 3 12AVR130 23 6 7 1 12AVR145L LLP 26 6 8 0 12AVR145ET 26 3 7 9 12AVR150ET 27 1 8 1 12AVR170ET 30 8 9 3 12AVR200ET 38 3 11 5 Max Min Charge Charge Current A Current A Battery Type Using minimum charge current will extend recharge time and increase risk of battery being undercharged ...

Page 8: ...______________________ Date Installed _____________________ Readings Taken By ____________________________ Remarks Recommendations __________________________________________________________ Readings should be taken at installation and annually thereafter _________________________________________________________________________________ 1 41 81 121 161 201 2 42 82 122 162 202 3 43 83 123 163 203 4 4...

Reviews: