background image

8

Capacity Testing

continued

The test is conducted by discharging a fully charged battery at
a specific rate until the battery voltage drops to a
predeter¬mined volts per battery, times the number of batter-
ies in the battery system. By noting the time elapsed between
when the battery was put on discharge and when the final volt-
age was reached, you can determine whether the battery is
delivering its rated capacity:

 1. Give the battery an equalizing charge until the current has

stabilized. Start the test and record the starting time.

 2. Record individual battery voltages and overall battery sys-

tem voltages during the first hour at 10 minutes, 30 min-
utes and then 60 minutes. After the first hour, take hourly
readings until the first battery voltage reaches 10.80 volts
per battery. From this point on, record the voltage of the
batteries every 5 minutes. monitor the voltage of the low
batteries and as the voltage of each battery drops below
the predetermined final voltage, record the time.

 3. When the majority of the batteries reach termination value,

stop the test. Don’t let any battery go into reversal.

For example, if the test was run at the 360 minute rate was ter-
minated after 336 minutes; the capacity percentage would be
93%

 4. If the battery system delivers 50% or more of its rated

capacity, it can be returned to service. If the test indicates
less than 50% of the battery’s rated capacity is being deliv-
ered, the battery system should be either repaired or
replaced, depending upon its age and overall condition.

For more detailed information on capacity testing, contact
East Penn Manufacturing Company or your local authorized
East Penn Representative.

GLOSSARY:

AGM – Absorbed Glass Mat –

A class of VRLA (Valve

Regulated Lead-Acid) battery in which the electrolyte is
absorbed into a glass mat. 

Ambient Temperature –

The average temperature of the 

battery room. Temperatures below 77°F (25°C) will reduce
battery capacity. Temperatures above 77°F (25°C) will
reduce battery service life.

Amp Hour (Ah) –

Amps times Hours

Battery Efficiency – The amount of Ah return required to
achieve full SOC vs. the amount of Ah removed during dis-
charge. Require 110% to 115% Ah return

Capacity –

The capacity of a battery is specified as the 

number of Amp-Hrs that the battery will deliver at a specific
discharge rate and temperature. The capacity of a battery is
not a constant value and is seen to decrease with increasing
discharge rate.

C

20

Battery capacity measured in Ah (amp hour) at the

20hr    rate.

End Voltage –

The minimum voltage at which a DC system

will operate. 

Flooded – A battery in which the products of electrolysis 
and evaporation are allowed to escape to the  atmosphere 
as they are generated. Electrolyte is free flowing throughout
the battery.

Gel –

A class of VRLA (Valve Regulated Leda-Acid) battery

in which the electrolyte is immobilized in a gel form (sulfuric
acid mixed with silica)

Parallel –

A circuit that provides more than one path for the

flow of current. A parallel arrangement of batteries (usually
of like voltages and capacities) has all positive terminals
connected to a conductor and all negative terminals con-
nected to another conductor. If two 12-volt batteries of 50
ampere-hour capacity each are connected in parallel, the 
circuit voltage is 12 volts, and the ampere-hour capacity of
the combination is 100 ampere-hours.

Series –

A circuit that has only one path for the flow of 

current. Batteries arranged in series are connected with 
negative of the first to positive of the second, negative of the
second to positive of the third, etc. If two 12-volt batteries of
50 ampere hours capacity each are connected in series, the
circuit voltage is equal to the sum of the two battery volt-
ages, or 24 volts, and the ampere-hour capacity of the com-
bination is 50 ampere-hours.

SOC (State of Charge) –

The amount of deliverable 

low-rate electrical energy stored in a battery at a given time
expressed as a percentage of the energy when fully charged
and measured under the same discharge conditions. If the
battery is fully charged the “SOC” is said to be 100%.

Temperature Correction –

A factor used to compensate for

battery capacity and/or adjust battery voltage at ambient
temperatures greater than or less than 77°F (25°C).  

Undercharge (Deficit charge) –

Charging a battery with less

ampere-hours (Ah) than is required to return the battery to
its initial state-of-charge. This results in a reduction in the
battery state-of-charge.

VPC –

Volts per Cell

VRLA –

Valve Regulated Lead Acid – a lead-acid cell/battery

that is sealed with exception of a valve that opens to the
atmosphere when the internal gas pressure exceeds atmos-
pheric pressure by a pre-selected amount. VRLA batteries
provide a means for recombination of internally generated
oxygen and the suppression of hydrogen gas evolution to
limit water consumption

Summary of Contents for SOLAR Monoblock VRLA System

Page 1: ...Monoblock VRLA System Installation Operating Manual ...

Page 2: ...n X Unpacking X Storage X Installation General X Grounding X System Operation Charging X Charging Parameters X Charge Current X State of Charge X Record Keeping Maintenance Annual Inspection X Rectifier Ripple X Capacity Testing X Glossary Appendix A Renewable Energy Worksheet X Appendix B Example of Typical 3 Stage Charger X Appendix C Depth of Discharge vs Freezing PointX Appendix D Capacity vs ...

Page 3: ...of Discharge DoD Depth of discharge is a function of design The deeper the discharge per cycle the shorter the life of the battery A cycle is a discharge and its subsequent recharge regardless of depth of discharge Systems should be designed for shallow discharges The result of shallower discharges is typically a larger capacity battery at prolonged battery life A Cycle vs DoD chart should be cons...

Page 4: ...ing the necessary maximum charge current for the system If the calculation shows the absorption time is greater than the minimum average peak sun hours for the installation location the amount of available current to the batteries should be increased which could be accomplished by a larger array or a secondary power source such as a generator Charge Current Verification FLOODED C20 x 0 44 charge c...

Page 5: ...equate space and accessibility for taking individual battery or cell voltage hydrometer readings and adding water should be considered If installed in an earthquake seismic zone battery racking system must be of sufficient strength and adequately anchored to the floor Battery rack design and anchoring should be reviewed by a structural engineer Ventilation It is the responsibility of the installer...

Page 6: ...ing no back up energy source Wiring connection assessment difficult to follow with multiple wirings connected to same battery terminal increasing chance of re connection wiring errors Common Bus Wiring a wiring scheme in which same polarity terminals are connected to a single termination point All inter connecting wiring should be of same length to minimize volt age drop Advantages Cables can be o...

Page 7: ...ring dry and clear of tools and other for eign objects 4 Provide adequate ventilation per IEEE standard 1187 and or local codes and follow recommended charging voltages 5 Never remove or tamper with the pressure relief valves except for cell replacement Warranty void if vent valve is removed 6 Inspect flooring and lifting equipment for functional adequacy 7 Adequately secure cell modules racks or ...

Page 8: ...g gently with a non metallic brush or pad before installing connectors No Ox ID grease can be used but is not required 3 Install all electrical connectors cables and bolting hard ware loosely to allow for final alignment of batteries Torque to manufacturer recommendations 4 After torquing read the voltage of the battery string to ensure the individual batteries are connected correctly The total vo...

Page 9: ...tage readings are affected by dis charge and recharges for cyclic applica tions the battery ies must be in a fully charged condition prior to taking readings Batteries should be within 0 30 volts 0 15 volts for 6V of the average battery float voltage 3 Record charger voltage 4 Record the ambient temperature 5 Record individual battery ohmic readings 6 Record all interunit and terminal connection r...

Page 10: ...nd temperature The capacity of a battery is not a constant value and is seen to decrease with increasing discharge rate C20 Battery capacity measured in Ah amp hour at the 20hr rate End Voltage The minimum voltage at which a DC system will operate Flooded A battery in which the products of electrolysis and evaporation are allowed to escape to the atmosphere as they are generated Electrolyte is fre...

Page 11: ...9 APPENDIX A Completing all parameters ensures accurate battery sizing Worksheet to be submitted to sales representative for battery recommendation ...

Page 12: ...10 APPENDIX B Example of typical 3 stage charger ...

Page 13: ...11 APPENDIX C Depth of Discharge vs Freezing Point ...

Page 14: ...12 APPENDIX D Capacity vs Operating Temperature ...

Page 15: ...13 APPENDIX E Voltage Compensation Chart 0 1 2 3 4235 4 65 Note 1 Above values based on 12 volt battery 2 Divide above values in half for 6 volt battery ...

Page 16: ...14 APPENDIX F Charging Current vs Charging Time chart Discharge Voltage Curve ...

Page 17: ...APPENDIX G ...

Page 18: ...ufacturing Co Subsidiary 1 800 372 9253 www mkbattery com e mail sales mkbattery com www dekabatteries com All data subject to change without notice No part of this document may be copied or reproduced electronically or mechanically without written permission from the company ...

Reviews: