DESIGNER’S HANDBOOK 4189350049C EN
Page 32 of 206
XDi type
Panel cut-out
Front size
Free depth below
panel surface,
XDi without
extension module
Free depth below
panel surface,
XDi with extension
module
XDi 192
186 mm (-0.0/+1.1 mm)
x
138 mm (-0.0/+1.0 mm)
196 x 148 mm
(wide as XL192)
Min. 60 mm
Rec. >75 mm
Min. 95 mm
Rec. >105 mm
4.2.2
Waterproof mounting
The XDi front, front glass and buttons are waterproof. Therefore, the protection around mounting screws and
between the XDi front flange and the surface of the panel where the XDi is mounted are the critical areas to obtain
the required IP protection.
The XDi is available with a factory-installed IP66 option for use in wet rooms, like a thruster room.
To obtain IP protection in general, the panel must be flat and smooth (not curved) where the XDi is mounted, and
please pay special attention to the accuracy of the cut-out and the tightening of the screws (do not overtighten).
In installations where IP protection is important, the IP66 option is required. If the requirement is IP52 or lower, the
standard XDi can be used.
For IP52, the panel surface where XDi is mounted must be completely flat and smooth. In practice, this is often not
the case and therefore a water resistant sealant should be used between the XDi front flange and the panel surface
to obtain the required protection. Alternatively, use the XDi with the IP66 option.
4.3
Mounting instructions
The XDi is very easy to mount:
1. Remove the front frame by gently pulling one corner (the frame is snapped on the front when you receive
the XDi unit)
2. Make the cut-out in your panel (see previous section).
3. Connect wires in connectors according to installation instructions.
4. Mount the connectors in the unit.
5. Use the cable tie to fixate the cables to the XDi unit (use cable support and cable relief on long cables
inside the panel)
6. Insert the unit from the front of the panel
7. Fixate it firmly by tightening the screws on the XDi front (see the smart-grip function on fig. 6 below).
The recommended screwdriver torque is: 0.5 Nm +/- 0.1 Nm
8. Connect power to the unit
9. Follow the setup wizard instructions
10. Write the assigned CAN Node ID number on the white label on the XDi front.
11. If needed, make setup adjustments
12. Mount the front frame again
13. Installation is completed
The detailed information about connections, wiring and setup can be found in the next chapters of this manual.
See the data sheet for detailed 2D drawings.
3D drawings (step files) for use in CAD systems are available on request, please contact
DEIF support.