18.4 Miscellaneous
18.4.1 Lamp test
The lamp test lights all the LEDs on the display unit. The test cycles through the LED colours for the time configured in the lamp test
parameters.
During the lamp test a message box is shown on the display unit.
Inputs
The table below describes optional inputs for the lamp test.
Assign the inputs under
Configure > Input/output
. Select the hardware module, then select the input to configure.
Table 18.13
Optional inputs for the lamp test
Function
I/O
Type
Details
Test functions > Lamp test > Start lamp
test
Digital input Pulse
Activating this input has the same effect as enabling the lamp
test
Activate
parameter.
Test functions > Lamp test > Stop lamp
test
Digital input Pulse
If this input is activated while a lamp test is in progress, the
controller stops the lamp test.
Configure the parameters under
Configure > Parameters > Test functions > Lamp test
.
Table 18.14
Lamp test parameters
Parameter
Range
Default
Comment
Activate
Not enabled,
Enabled
Not enabled
Not enabled
: There is no lamp test.
Enabled
: When the parameter is saved, the lamp test starts. After the lamp
test, the controller automatically changes the parameter to
Not enabled
.
DESIGNER'S HANDBOOK 4189340911K UK
Page 496 of 521