Description of options 

 

  Description of option 

 

  Functional description 

 

  Parameter list 

 

 

DEIF A/S, Frisenborgvej 33 

Tel.: +45 9614 9614, Fax: +45 9614 9615 

DK-7800 Skive, Denmark 

E-mail: [email protected], URL: www.deif.com 

 

Summary of Contents for Multi-line 2

Page 1: ...line 2 version 2 4189340286F SW version 2 4X X Description of options Description of option Functional description Parameter list DEIF A S Frisenborgvej 33 Tel 45 9614 9614 Fax 45 9614 9615 DK 7800 Skive Denmark E mail deif deif com URL www deif com ...

Page 2: ...ITIONS 3 2 DESCRIPTION OF OPTION 4 OPTION O1 4 TERMINAL DESCRIPTION 4 WIRING 6 3 FUNCTIONAL DESCRIPTION 8 TURBINE OPERATION 8 WATER LEVEL REGULATION 8 REGULATION PRINCIPLE 10 JET DEFLECTOR 12 TURBINE REGULATION 14 SEQUENCES 15 DIGITAL INPUT 16 INHIBIT 17 4 PARAMETER LIST 19 This manual is valid for standard multi line 2 PPU GPC units with firmware version 2 32 0 or later ...

Page 3: ... and voltages Therefore the installation should only be carried out by authorised personnel who understand the risks involved in working with live electrical equipment Definitions Throughout this document a number of notes and warnings will be presented To ensure that these are noticed they will be highlighted in order to separate them from the general text Notes Warning The notes provide general ...

Page 4: ...nput PCB Term Function Description 126 Input 5 common Common 127 Analogue input 5 4 20mA in for water level control 128 Input 6 common Common 129 Analogue input 6 4 20mA in 130 Input 7 common Common 131 Analogue input 7 4 20mA in 132 Input 8 common Common 133 Analogue input 8 4 20mA in The 4 20mA input no 5 must be used for water level input The 4 20mA inputs no 6 7 and 8 can only be used as alarm...

Page 5: ...50V AC 8A 19 NC 20 Open collector 1 Transistor out Pulse output 1 kWh counter 21 Open collector 2 Transistor out Pulse output 2 kvarh counter 22 Com Common Common terminal for terminals 20 and 21 23 Binary input Optocoupler Remote alarm inhibit configurable 24 Binary input Optocoupler Remote alarm acknowledge configurable 25 Binary input Optocoupler Start sync control functions configurable 26 Bin...

Page 6: ...ol T urbine G AVR 5 6 7 R elay 1 Jet Deflectors Multi line 2 17 18 19 14 15 16 GCB Relay 4 Open GCB Sync 3 3 Valve 1 Valve 2 Valve 3 Valve 4 3 24VDC BUS BAR Start Sync Contr Deload 25 43 65 66 67 68 127 126 4 20mA Water Level Speed Up Speed Down Jet Deflector Feedback 23 or 24 or 26 or 27 Closed 28 56 ...

Page 7: ...ol T urbine G AVR 5 6 7 Relay 1 Jet Deflectors Multi line 2 17 18 19 14 15 16 GCB Relay 4 Open GCB Sync 3 3 Valve 1 Valve 2 Valve 3 Valve 4 3 24VDC BUS BAR Start Sync Contr Deload Jet Deflector Feedback 25 43 127 126 4 20mA Water Level 23 or 24 or 26 or 27 Closed 66 67 66 67 70 71 91 92 95 96 28 56 ...

Page 8: ...F Menu 4131 must be OFF Droop OFF ON Load sharing ON ON Fixed water level control ON OFF Menu 4131 must be ON Water level regulation The water level regulation must be used if the regulation depends on the water level in the reservoir which contains the water that drives the turbine Activate water level control To activate the water level regulation the mode input 1 must be activated and the menu ...

Page 9: ...ption Comments 404X Water level nominal This value corresponds to the 20mA value of the transducer 404X Water level minimum This value corresponds to the 4mA value of the transducer This can be adjusted from the USW or from the display The 4mA value can be adjusted negative This is to be able to stop the regulation see the description of Water level regulation on page 10 ...

Page 10: ...41 2 The water level transducer gives 20mA when the water level is above 180 menu 404X 3 The water level transducer gives 4mA when the water level is below 60 menu 404X This can only be adjusted from the USW Adjust the water level corresponding to the 20mA value Adjust the water level corresponding to the 4mA value The input can only be scaled in percent If the scaling is not done according to the...

Page 11: ...be reduced in the lower end by adjusting the 4mA value to a negative value The power will not be regulated into the area where the water level is negative The purpose of this is partly to avoid the generator to go into reverse power and partly to keep the turbine in the economic operating range The operating range of the turbine can be reduced in the high end by decreasing the PSET menu 4041 to a ...

Page 12: ...hanges to open water bypass position The principle looks like this jet deflector shown in closed position Jet deflector Water inlet To turbine bypass Holding magnet Moving weight Closed position Open position Relay selection The relay used for the jet deflector is the relay 1 Terminal 5 6 7 see extract from I O list below Term Function Technical data Description 5 NO Relay 1 Configurable jet defle...

Page 13: ...lay is to open the deflector whenever the multi line 2 is without power or when the watch dog of the device detects a fault The status relay is a normally closed relay When the GPC PPU is in good functioning condition the relay is energized The status relay is only for DC voltage When the multi line 2 is without power relay 1 output will be in the closed deflector valve position To open the deflec...

Page 14: ...le Option D1 NOT selected Option D1 selected Function Output Cascade Voltage control Cascade Voltage control Output 66 67 X X Output 70 71 X X Output 91 92 X X Output 95 96 X Not available X Analogue control valves parallel w mains generator The cascade works like this At turbine start all outputs are 0mA As the speed load set point increases the cascade 1 will give increasing signal until reachin...

Page 15: ...RPM is needed In this case the output curves look like this There can be up to 4 analogue outputs for cascade control of loads Sequences Turbine start Due to the slow start up of a turbine the function in menu 2255 Turbine start timer has been added The turbine start function can be used in connection with relay outputs only This timer represents the time where the speed UP signal is active if no ...

Page 16: ...ker closes 4 Power and possibly power factor control for parallel w mains or frequency control for island Stop sequence The stop sequence consists of three steps 1 Ramp down generator to load 0 kW 2 Open breaker 3 Close all control valve s Shutdown sequence The shutdown sequence consists of three steps 1 Generator breaker trip 2 Jet deflector open bypass water flow 3 Shut control valves Digital In...

Page 17: ... the icon on the horizontal toolbar When selecting Inputs Outputs this dialog box appears In the example of the configuration above the Deflector closed feedback can be changed to terminals 23 24 26 or 27 Inhibit The inhibit functionality is described in the Designer s Reference Handbook The functionality varies if the inhibit has been configured manually through the configuration tool in the USW ...

Page 18: ...GPC PPU Option O1 Water turbine control DEIF A S Page 18 of 19 When stopping the turbine the alarms will not be deactivated before the generator voltage has dropped to 30 UNOMINAL ...

Page 19: ...ting 3531 4 20mA in no 5 2 Set point 0 0 250 0 10 3532 4 20mA in no 5 2 Time 0 2 s 100 0 s 10 0 s 3533 4 20mA in no 5 2 Relay output A R0 none R2 3534 4 20mA in no 5 2 Relay output B R0 none Option dependent R0 3535 4 20mA in no 5 2 Enable OFF ON OFF 4040 Power settings No Setting Min setting Max setting Factory setting 4041 Controller settings P Fixed power set point 0 100 100 4042 Controller set...

Reviews: