2. Mounting
2.1 GCU 100 mounting
2.1.1 Mounting of the unit
Included in the package is 12 fixing clamps.
The unit is designed for flush mounting for both IP52 and IP65 mounting. For IP52, four fixing clamps are to
be used; two at the top and two at the bottom.
For IP65, all 12 clamps must be mounted to comply with the rating.
2.1.2 Unit dimensions and panel cutout
The unit is designed for mounting in the panel front.
In order to ensure optimum mounting, the panel door must be cut out according to the following measure-
ments:
H × W = 151.00 × 211.00 + 1.00 mm
H × W = 5.94" × 8.31" + 0.04"
Dimensions are in mm (inches) and valid for GCU 111/112/113.
GCU 100 installation instructions
4189340799 UK
Mounting
DEIF A/S
Page 5 of 31