OPERATOR'S MANUAL

Compact Genset Controller, CGC 400

● Push-buttons
● LEDs
● Display and menu structure
● Display readings
● Alarm handling and log list

Document no.: 4189340787A
SW version: 1.00

Summary of Contents for AGC 100

Page 1: ...j 33 DK 7800 Skive Tel 45 9614 9614 Fax 45 9614 9615 info deif com www deif com 45 9614 9614 Fax 45 9614 9615 info deif com www deif com OPERATOR S MANUAL Compact Genset Controller CGC 400 Push buttons LEDs Display and menu structure Display readings Alarm handling and log list Document no 4189340787A SW version 1 00 ...

Page 2: ...3 Contents and overall structure 4 2 Push buttons and LEDs 2 1 Push button functions 5 2 2 LED functions 6 3 Display and menu structure 3 1 Menu 7 3 1 1 Menu system 7 3 1 2 View menu 7 3 1 3 Menu structure example 8 3 2 Display functions 9 3 2 1 Functional examples 9 4 Status line text 4 1 Status line text 11 4 1 1 Standard texts 11 5 Running modes 5 1 Running mode overview 13 6 Alarm handling and...

Page 3: ...n or the operation of the set must be contacted The unit is not to be opened by unauthorised personnel If opened anyway the warranty will be lost Disclaimer DEIF A S reserves the right to change any of the contents of this document without prior notice 1 1 3 Safety issues Installing and operating the unit may imply work with dangerous currents and voltages Therefore the instal lation should only b...

Page 4: ... is to give the operator important information to be used in the daily operation of the unit Please make sure to read this document before starting to work with the unit and the generator set to be controlled Failure to do this could result in human injury or damage to the equip ment 1 2 2 Intended users This Operator s Manual is mainly intended for the daily user On the basis of this document the...

Page 5: ...ter value acknowledges alarm 4 Back button 4 Remove pop up messages 5 Manual Block running mode selector 5 Press MAN twice to activate Block mode 6 Lamp test 7 AUTO running mode selector 8 Test running mode selector 9 Close mains breaker 10 Open mains breaker 11 Close generator breaker 12 Open generator breaker 13 Start engine manual running mode 14 Stop engine manual running mode 15 Reset horn re...

Page 6: ... alarms are present 3 4 x LED 4 x LEDs with selectable indication function Selection is made in M Logic 4 MAN LED steady light indicates that Manual mode is active LED flashing green indicates that Block mode is active 5 AUT LED indicates that Auto mode is active 6 Mains OK LED is green if the mains is present and OK LED is red at a mains failure LED is flashing green when the mains returns during...

Page 7: ... be acknowl edged by pressing the OK button Service menu This menu contains input output M Logic status and data about the unit 3 1 2 View menu The view menus are the daily use menus for the operator There are 20 configurable display views with up to three configurable display lines in each view View configuration is done through the PC utility software USW In the view menus various measured value...

Page 8: ... 1 Auto start stop 1 Service menu Digital in 11 0 Digital in 12 0 Digital in 13 0 Alarm list Ch 1981 UNACK 1 2 alarm s GB Ext tripped Event log GB ON 1 50 Log s 2012 10 01 08 15 00 Event log LOG MENU Alarm log Battery test log G U L1L2 ISLAND MODE G U L2L3 G U L3L1 Run absolute Alarm list Ch 4570 UNACK 2 2 alarm s Start failure Use arrows to toggle betweeen menus G U L1L2 400 V ISLAND MODE G U L2L...

Page 9: ...solute 0 hrs Service timer 1 and 2 Run hours Alarm acknowledge G U L1L2 ISLAND MODE G U L2L3 G U L3L1 G f L1 Press the OK button to enter the list of active alarms Alarm list Ch 1270 UNACK 1 1 alarm s BB U 1 The alarm list shows the active alarms Press the OK button to ackowl edge alarms Parameter settings G U L1L2 ISLAND MODE G U L2L3 G U L3L1 G f L1 Press the OK button to enter the parameter set...

Page 10: ...dit value with up and down arrows and save the value by pressing the OK button For detailed information about changing parameters and setup please see the Designer s Ref erence Handbook CGC 400 Operator s manual 4189340787 UK Display and menu structure DEIF A S Page 10 of 14 ...

Page 11: ...ED FOR START Generator stopped and active alarm s on the genera tor GB ON BLOCKED Generator running GB open and an active Trip GB alarm SHUTDOWN OVERRIDE The configurable input is active ACCESS LOCK The configurable input is activated and the operator tries to activate one of the blocked keys GB TRIP EXTERNALLY Some external equipment has tripped the breaker An external trip is log ged in the even...

Page 12: ...equency is OK after a mains failure The timer shown is the Mains OK delay Hz V OK IN s The voltage and frequency on the genset is OK When the timer runs out it is allowed to op erate the generator breaker COOLING DOWN s Cooling down period is activated COOLING DOWN Cooling down period is activated and infinite Cooling down timer is set to 0 0 s GENSET STOPPING This info is shown when cooling down ...

Page 13: ... when the test mode is selected The type of test is selected in parameter 7040 Manual Manual means that the unit will not initiate any sequences automatically as is the case with the auto mode It will only initiate sequences if external signals are given Block When the block mode is selected the unit is not able to initiate any sequences e g the start sequence Block mode must be selected when main...

Page 14: ...ly one alarm at a time Therefore all other alarms are hidden Alarm list Ch 1270 UNACK 1 1 alarm s BB U 1 To see the other alarms use the up and down push buttons to scroll in the display To acknowledge an alarm press OK button 6 2 Log list The log is divided into three different lists 1 Event log 2 Alarm log 3 Battery test log The log list contains up to 50 events the alarm list contains up to 30 ...