Sensor200 USER MANUAL 62360MN000-A00
37 of 40
Review the firmware update procedure carefully before you begin. The firmware update
procedure must be allowed to complete without interruption. If the update procedure is
interrupted by user interference, a power failure, or some other circumstance, the existing
firmware may be corrupted, and the device may become nonfunctional. Contact Degree
Controls if your Rooster
TM
is inoperative as a result of an interruption during the firmware
update procedure.
Soft Reboot from Info Screen
Procedure:
1.
Insert the USB thumb drive into the left side of Rooster
TM
.
2.
Navigate to the Info [
] screen and press the Upgrade [
]button at the bottom of
the screen. Rooster™ will prompt you to confirm you wish to backup current settings and
upgrade the firmware.
3.
Select “Yes”. Rooster™ will restart to read the USB thumb drive, and the Alarm LED turns
on. Once the upgrade process i
s complete, Rooster™ will automatically restart.
4.
Navigate to the Info screen to validate that the new firmware version was properly
installed. The firmware release information
–
listed next to “firmware”
- should have
changed to the most current build. If this is not the case, repeat the upgrade procedure.
Power Cycle Procedure
Procedure:
1.
Remove power from the Rooster
TM
.
2.
Insert USB thumb drive into left side of the Rooster
TM
.
3.
Depress and hold the
“Home”
button, while reapplying power to your unit. (Hard Home
button must be depressed while Rooster
TM
powers up in order to enter the firmware
update sequence.)
4.
After approximately 3 seconds, release the Home button. After approximately 10
seconds, the LED on the front of the Rooster
TM
will light, and the unit will boot up with
the new firmware.
5.
When the field upgrade procedure is complete, navigate to the Info [
] screen to
validate that the new firmware version was properly installed. The firmware release
information
–
listed next to “firmware”
- should have changed to the most current build.
If this is not the case, repeat the upgrade procedure.
Factory Reset Procedure
The Factory Reset will return the Rooster
TM
Sensor200 to its default alarm and input/output
settings. Time and date will be preserved. Factory Reset Procedure can be done at any time
upon system reset to restore default settings and passwords.
1.
When the 1
st
information screen displays, momentarily press the
“Mute” key
.