Deep Sea Electronics Plc DSE7310 MKII Installation Instructions And Operators Manual Download Page 2

MAIN CONFIGURATION EDITOR PARAMETERS 

 

NOTE: Depending upon module configuration, some values in the Main & 

Running Configuration Editors may not be available. For more information refer to 
DSE publication 057-243  DSE7310 MKII & DSE7320 MKII Configuraiton Suite PC 
Software Manual
 available from www.deepseaplc.com 

 

Section 

Parameter As Shown On Display 

Value 

Display 

Contrast 

0 % 

 

Language 

English  

 

Current Date and Time 

Month, Year, hh:mm

 

 

Dual Mutual Mode 

Engine Hours / Dual Mutual 
Hours / Priority

 

 

Dual Mutual Priority 

 

Dual Mutual Duty Time 

0 h 0 m 

Editor 

Config To Edit 

Main Configuration / 
Alternative Configuration 
1,2,3,4,5 

 

Default Configuration 

Main Configuration / 
Alternative Configuration 
1,2,3,4,5 

Engine 

Oil Pressure Low Shutdown 

0.00 bar 

Oil Pressure Low Pre Alarm 

0.00 bar 

 

Coolant Temperature Low Warning 

0 ºC 

Coolant Temperature High Pre Alarm 

0 ºC 

 

Coolant Temperature High Electrical Trip  0 ºC 

 

Coolant Temperature High Shutdown 

0 ºC 

 

Fuel Usage Alarm (Running Rate) 

0 % 

 

Fuel Usage Alarm (Stopped Rate) 

0 % 

Specific Gravity 

0.00 

 

Pre Heat Temperature 

0 ºC 

 

Post Heat Timer 

0 h 0 m 0 s 

 

Pre Heat Timer 

0 h 0 m 0 s 

 

Post Heat Temperature 

0 ºC 

 

Droop Control 

Active / Inactive 

 

Droop Control 

0 % 

 

Engine Under Speed Shutdown 

Active / Inactive 

 

Engine Under Speed Shutdown 

0 RPM 

 

Engine Under Speed Warning 

Active / Inactive 

 

Engine Under Speed Warning 

0 RPM 

 

Engine Under Speed Delay 

0.0 s 

 

Engine Over Speed Warning 

Active / Inactive 

 

Engine Over Speed Warning 

0 RPM 

 

Engine Over Speed Shutdown 

0 RPM 

 

Engine Over Speed Delay 

0.0 s 

 

Engine Speed Overshoot 

0 % 

 

Engine Speed Overshoot Delay 

0.0 s 

 

Battery Under Voltage Warning 

Active / Inactive 

 

Battery Under Voltage Warning 

0 V 

 

Battery Under Voltage Warning Delay 

0 h 0 m 0 s 

 

Battery Over Voltage Warning 

Active / Inactive 

 

Battery Over Voltage Warning 

0 V 

 

Battery Over Voltage Warning Delay 

0 h 0 m 0 s 

 

Charge Alternator Failure Warning 

Active / Inactive 

 

Charge Alternator Failure Warning 

0 V 

 

Charge Alternator Warning Delay 

0 h 0 m 0 s 

 

Charge Alternator Failure Shutdown 

Active / Inactive 

 

Charge Alternator Failure Shutdown 

0.0 V 

 

Charge Alternator Shutdown Delay 

0 h 0 m 0 s 

Generator 

AC System 

3 Phase, 4 Wire 

 

Generator Under Voltage Shutdown 

0 V 

 

Generator Under Voltage Pre Alarm 

0 V 

 

Generator Under Voltage Delay 

0.0 s 

 

Generator Nominal Voltage  

0 V 

 

Generator Over Voltage Pre Alarm 

0 V 

 

Generator Over Voltage Shutdown 

0 V 

 

Generator Over Voltage Delay 

0.0 s 

 

Generator Under Frequency Shutdown 

0.0 Hz 

 

Generator Under Frequency Pre Alarm 

0.0 Hz 

 

Generator Under Frequency Delay 

0.0 s 

 

Generator Nominal Frequency  

0.0 Hz 

MAIN CONFIGURATION EDITOR PARAMETERS (CONTINUED) 

 

Section 

Parameter As Shown On Display 

Value 

Generator 

Generator Over Frequency Pre Alarm 

0.0 Hz 

(Continued) 

Generator Over Frequency Shutdown 

0.0 Hz 

 

Generator Under Frequency Delay 

0.0 s 

 

Generator Over Frequency Overshoot 

0 % 

 

Generator Over Frequency Overshoot 
Delay 

0.0 s 

 

Generator CT Primary Current 

0 A 

 

Generator Secondary Current 

1 A / 5 A 

 

Generator CT Primary Earth Current 

0 A 

 

Full Load Rating 

0 A 

 

Delayed Over Current 

Active / Inactive 

 

Delayed Over Current 

0 % 

 

Generator Earth Fault Trip 

Active / Inactive 

 

Generator Earth Fault Trip 

0 % 

 

kW Overload Trip 

0 % 

Mains 

Mains Under Voltage Trip 

0 V 

DSE7320 MKII  

Mains Over Voltage Trip 

0 V 

Only 

Mains Under Frequency Trip 

0.0 Hz 

 

Mains Over Frequency Trip 

0.0 Hz 

Timers 

Start Delay Off Load 

0 h 0 m 0 s 

 

Start Delay On Load 

0 h 0 m 0 s 

 

Start Delay Mains Fail 

0 h 0 m 0 s 

 

Start Delay Telemetry 

0 h 0 m 0 s 

 

Mains Transient Delay 

0 m 0 s 

 

Crank Duration Timer 

0 m 0 s 

 

Crank Rest Timer 

0 m 0 s 

 

Smoke Limiting 

0 m 0 s 

 

Smoke Limiting Off 

0 m 0 s 

 

Safety On Delay 

0 m 0 s 

 

Warm Up Timer 

0 h 0 m 0 s 

 

Transfer Time 

0 m 0.0 s 

 

Return Delay 

0 h 0 m 0 s 

 

Cool Down Timer 

0 h 0 m 0 s 

 

Fail To Stop Delay 

0 m 0 s 

 

LCD Page Timer 

0 h 0 m 0 s 

 

Auto Scroll Delay 

0 h 0 m 0 s 

 

Sleep Timer 

0 h 0 m 0 s 

 

Backlight Power Save 

0 h 0 m 0 s 

Schedule 

Schedule 

Active / Inactive 

 

Schedule Bank 1 Period  

Weekly / Monthly,  

 

On Load / Off Load / Auto Start Inhibit, 
Week, Start Time, Run Time and Day  
Selection (1-8) 

Press 

 to begin editing then 

up or down when selecting the 
different parameters. 

 

Schedule Bank 2 Period  

Weekly / Monthly,  

 

On Load / Off Load / Auto Start Inhibit, 
Week, Start Time, Run Time and Day 
Selection (1-8) 

Press 

 to begin editing then 

up or down when selecting the 
different parameters. 

 

ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR 

 

 

The ‘running’ editor can be entered while the engine is running. All protections remain 
active if the engine is running while the running editor is entered. 

 

Press and hold the 

  (Tick) button to enter the running editor. 

 
 
RUNNING CONFIGURATION EDITOR PARAMETERS 
 

Section 

Parameter As Shown On Display 

Values 

Display 

Contrast 

0 % 

 

Language 

English  

Dual Mutual 

Dual Mutual Priority 

Engine

 

Manual Frequency Trim  

0.0 Hz 

Speed Bias  

0.0 

Governor Gain  

0   

Frequency Adjust 

0.0 % 

DPF Auto Regen Inhibit  

Active / Inactive 

DPF Manual Regeneration Request  

Active / Inactive 

ECU Service Mode 

Active / Inactive 

 
 
DIMENSIONS AND MOUNTING 
 
DIMENSIONS 

245 mm X 184 mm X 51 mm  
(9.6” X 7.2” X 2.0”) 

 

PANEL CUTOUT  

220 mm X 160 mm  
(8.7” X 6.3”) 

 

WEIGHT 

0.98 kg  
(2.16 lb)

 

TEMPERATURE 

Operating: -40 ºC to +70 ºC  
                  (-40 ºF to +158 ºF) 
 
Storage: -40 ºC to +80 ºC  
               (-40 ºF to +176 ºF)

 

 

 

 

 
 

 

REQUIREMENTS FOR UL CERTIFICATION 

 

WARNING!: More than one live circuit exists, see diagram overleaf for further information.  

 

Specification 

Description 

Screw Terminal Tightening Torque 

  4.5 lb-in (0.5 Nm) 

Conductors 

  Terminals suitable for connection of conductor size 13 AWG to 20 AWG (0.5 mm² to 2.5 mm²). 

  Conductor protection must be provided in accordance with NFPA 70, Article 240 

  Low voltage circuits (35 V or less) must be supplied from the engine starting battery or an isolated secondary circuit. 

  The communication, sensor, and/or battery derived circuit conductors shall be separated and secured to maintain at least ¼” (6 mm) separation from the 

generator and mains connected circuit conductors unless all conductors are rated 600 V or greater. 

Current Inputs 

  Must be connected through UL Listed or Recognized isolating current transformers with the secondary rating of 5 A max.   

Communication Circuits 

  Must be connected to communication circuits of UL Listed equipment 

DC Output Pilot Duty 

  0.5 A 

Mounting 

  Suitable for flat surface mounting in Type 1 Enclosure Type rating with surrounding air temperature -22 ºF to +122 ºF (-30 ºC to +50 ºC) 

  Suitable for pollution degree 3 environments when voltage sensing inputs do not exceed 300 V. When used to monitor voltages over 300 V device to be 

installed in an unventilated or filtered ventilation enclosure to maintain a pollution degree 2 environment. 

Operating Temperature 

  -22 ºF to +122 ºF (-30 ºC to +50 ºC) 

 