Deep Sea Electronics Plc 720 Installation Instructions And Operators Manual Download Page 2

 

 
 
 
 
 

Factory default settings are in bold italicised text. 

Auxiliary Input settings 

23 - Auxiliary Input 1 

0 - Delayed, warning close to activate 

 

1 - Delayed, warning, open to active 

 

2 - Immediate, warning, close to activate 

 

3 - Immediate, warning, open to activate 

 

4 - Delayed, shutdown, close to activate 

 

5 - Delayed, shutdown. Open to activate 

 

6 - Immediate, shutdown, close to activate 

 

7 - Immediate, shutdown, open to activate 

 

8 - Lamp test, close to activate 

 

9 - Lamp test, open to activate 

24 - Auxiliary input 1 delay 

0-10s (0s) 

25 - Auxiliary Input 2  

0 - Delayed, warning, close to activate 

 

1 - Delayed, warning, open to active 

 

2 - Immediate, warning, close to activate 

 

3 - Immediate, warning, open to activate 

 

4 - Delayed, shutdown, close to activate 

 

5 - Delayed, shutdown. Open to activate 

 

6 - Immediate, shutdown, close to activate 

 

7 - Immediate, shutdown, open to activate 

 

8 - Electrical trip, close to activate 

 

9 - Electrical trip, open to activate 

26 - Auxiliary input 2 delay 

0-10s (0s) 

Outputs  

 

27 - Auxiliary Output 1 

0 - Unused 

 

1 - Preheat Mode 0 

 

2 - Air Flap 

 

3 - Close Generator 

 

4 - Energise to stop 

 

5 - Engine Running 

 

6 - Shutdown Alarm 

 

7 - System in auto 

 

8 - Auxiliary input 1 active 

 

9 - Auxiliary input 2 active 

 

10 - Preheat mode 1 

 

11 - Preheat mode 2 

 

12 - Preheat mode 3 

 

13 - Warning Alarm 

 

14 - Common Alarm 

 

15 - Fail to start 

28 - Auxiliary Output 2  

0 - Unused 

 

1 - Preheat Mode 0 

 

2 - Air Flap 

 

3 - Close Generator 

 

4 - Energise to stop 

 

5 - Engine Running 

 

6 - Shutdown Alarm 

 

7 - System in auto 

 

8 - Auxiliary input 1 active 

 

9 - Auxiliary input 2 active 

 

10 - Preheat mode 1 

 

11 - Preheat mode 2 

 

12 - Preheat mode 3 

 

13 - Warning Alarm 

 

14 - Common Alarm 

 

15 - Fail to start 

 

Factory default settings are in bold italicised text. 

LCD Indicators 

 

29 - LCD indicator 1 

0 - Unused 

 

1 - Preheat Mode 0 

 

2 - Air Flap 

 

3 - Close Generator 

 

4 - Energise to stop 

 

5 - Engine Running 

 

6 - Shutdown Alarm 

 

7 - System in auto 

 

8 - Auxiliary input 1 active 

 

9 - Auxiliary input 2 active 

 

10 - Preheat mode 1 

 

11 - Preheat mode 2 

 

12 - Preheat mode 3 

 

13 - Warning Alarm 

 

14 - Common Alarm 

 

15 - Fail to start 

30 - LCD indicator 2 

0 - Unused 

 

1 - Preheat Mode 0 

 

2 - Air Flap 

 

3 - Close Generator 

 

4 - Energise to stop 

 

5 - Engine Running 

 

6 - Shutdown Alarm 

 

7 - System in auto 

 

8 - Auxiliary input 1 active 

 

9 - Auxiliary input 2 active 

 

10 - Preheat mode 1 

 

11 - Preheat mode 2 

 

12 - Preheat mode 3 

 

13 - Warning Alarm 

 

14 - Common Alarm 

 

15 - Fail to start 

 

 

NOTE:-  

The ‘preheat modes’ selectable for 

configurable outputs and LCD indicators perform the 
following actions : 
 

 

Preheat mode 0 - Preheat during preheat timer, 
ceasing at end of preheat timer. 

 

Preheat mode 1 - Preheat during preheat timer and 
continue until engine stops cranking. 

 

Preheat mode 2 - Preheat during preheat timer and 
continue until the safety delay timer has expired. 

 

Preheat mode 3 - Preheat during preheat timer and 
continue until the warming timer has expired. 

 
In addition, in all preheat modes, preheat takes place during 
the crank rest timer between crank cycles.

 

 

Misc 

 

31 - Full Load Current 
Rating 

5-6000A (500A) 

32 - Current 
Transformer Primary 

5-6000A (500A) 

33 - Alternator Poles 

2,4,6,8 (4) 

34 - AC Topology (see 
note 1) 

0 - 3 phase, 4 wire 

 

1 - Single phase, 2 wire 

35 - Oil Pressure 
Display Units  

0 - Bar / PSI 

 

1 - Kpa 

36 - Oil pressure 
sender type 

0 - Not used 

 

1 - Digital closed for low oil 
pressure 

 

2 - Digital open for low oil 
pressure 

 

3 - VDO 5 bar 

 

4 - VDO 10 bar 

 

5 - Datcon 5 bar 

 

6 - Datcon 10 bar 

 

7 - Datcon 7 bar 

 

8 - Murphy 7 bar 

 

9 - User configured 

37 - Coolant 
temperature sender 
type 

1 - Digital closed for high 
temperature 

 

2 - Digital open for high 
temperature 

 

3 - VDO 120 C 

 

4 - Datcon high 

 

5 - Datcon low 

 

6 - Murphy 

 

7 - Cummins 

 

8 - User configured 

 

Mains 

 

38 - Immediate Mains 
Dropout 

0 - No 

 

1 - Yes 

39 - Mains Undervolt Trip 

50-333V (184V) 

40 - Mains Undervolt Return 

50-333V (207V)  

41 - Mains Overvolt Return 

50-333V (253V) 

42 - Mains Overvolt Trip 

50-333V (276V) 

43 - Mains Transient Delay 
Timer 

0-30s (0s) 

 