SETTINGS
Factory default settings are in bold italicised text.
Timers
0 - Start Delay
0-60m (5s)
1 - Preheat
0-60s (0s)
2 - Cranking Time
3-60s (10s)
3 - Crank Rest Time
3-60s (10s)
4 - Safety On Delay
8-60s (8s)
5 - Warm Up Time
0-10m (0s)
6 - Gen transient delay
0-10s (0s)
7
–
Return Delay
0-60m (30s)
8 - Cooling Time
0-30s (1m)
9 - ETS Hold Time
0-60s (0s)
10 - Fail To Stop Delay Time
10-60s (60s)
11 - Low DC Voltage Alarm Delay
0-60m (5m)
NOTE:- Setting a timer to 0 will disable it
(where applicable)
Generator
12 - Under Frequency
0-60Hz (40Hz)
13 - Loading Frequency
20-60Hz (47Hz)
14 - Over Frequency
50-72Hz (57Hz)
15 - Loading Voltage
50-333V (212V)
16 - Over Current Alarm
50-120% (110%)
17 - Over Current Alarm Type
0 - Warning
1 - Shutdown
2 - Electrical Trip
Engine
18 - Low DC Voltage Alarm
0-25V (8V)
19 - Charge Fail Voltage Alarm
0-25V (8V)
Fixed Input settings
20 - Low Oil Pressure
5-150PSI (15 PSI)
21 - High Engine Temperature
90-150 C (95 C)
22 - Remote Start /
Simulated Mains input
0 - Remote start
close to activate
1 - Remote start
open to activate
2 - Simulated mains
close to activate
3 - Simulated mains
open to activate
ACCESSING THE CONFIG EDITOR
Press the Stop/Reset
and Info
buttons
simultaneously.
The LED beside the AUTO button will
flash continuously to indicate that
configuration mode has been entered.
The first configuration
setting is displayed:
From the configuration table, this example is
displaying Start Delay (parameter 0). It is currently
set to 5 seconds.
EDITING A PARAMETER
Enter the editor as described above.
Press + / - to scroll through the parameters to
the one you want to change.
Press
to enter edit
mode. The
symbol
will flash on the display
to indicate that edit
mode has been entered.
Press + / - to change the value to the desired
parameter.
Press
to save the value and exit edit mode for
this parameter.
The
symbol will be removed from the display
to indicate that edit mode has been exited.
To select another value to edit, press the + / -
buttons. Continuing to press the + and
–
buttons
will cycle through the adjustable parameters as
shown in the following lists.
D E E P S E A E L E C T R O N I C S
Model 720 Configuration and installation instructions
053-005
ISSUE 2
NOTE: To exit the front panel configuration editor at any time, press the Stop/Reset
button.
Ensure you have saved any changes you have made by pressing the
button first
DIMENSIONS
209mm x 146mm (8.23” x 5.75”)
MOUNTING
Mounting holes suitable for 4 x 4mm screws
Mounting Hole spacing 196.0mm x 103.5mm (7.717” x 4.075”)
PANEL CUT-OUT
182mm x 137mm (7.17” x 5.39”)
Maximum panel thickness
–
8mm (0.3”)
TYPICAL WIRING DIAGRAM
Deep Sea Electronics Plc.
Tel:+44 (0)1723 890099
Fax: +44 (0)1723 893303
LO CALL (from UK BT landlines) :
Telephone 0845 260 8933
Email: [email protected]
Web: www.deepseaplc.com
Deep Sea Electronics inc.
Phone: +1 (815) 316-8706
Fax: +1 (815) 316- 8708
TOLL FREE (USA only) : Tel: 1 866 636 9703
Email: [email protected]
Web: www.deepseausa.com
Deep Sea Electronics Plc.
(Far East)
Tel:+66 2 670 6228
Fax: +66 2 678 3028
Email: [email protected]
Web: www.deepseaplc.com
http://bestgenerator.spb.ru/?page_id=6765