SETTINGS 

Factory default settings are in bold italicised text. 
 

Timers 

 

0 -  Start Delay 

0-60m (5s) 

1 - Preheat  

0-60s (0s) 

2 - Cranking Time 

3-60s (10s) 

3 - Crank Rest Time 

3-60s (10s) 

4 - Safety On Delay 

8-60s (8s) 

5 - Warm Up Time 

0-10m (0s) 

6 - Gen transient delay 

0-10s (0s) 

 Return Delay 

0-60m (30s) 

8 - Cooling Time 

0-30s (1m) 

9 - ETS Hold Time 

0-60s (0s) 

10 - Fail To Stop Delay Time 

10-60s (60s) 

11 - Low DC Voltage Alarm Delay 

0-60m (5m) 

 
 

NOTE:- Setting a timer to 0 will disable it

 (where applicable)  

 
 

Generator 

 

12 - Under Frequency 

0-60Hz (40Hz) 

13 - Loading Frequency 

20-60Hz (47Hz) 

14 - Over Frequency 

50-72Hz (57Hz) 

15 - Loading Voltage 

50-333V (212V) 

16 - Over Current Alarm  

50-120% (110%) 

17 - Over Current Alarm Type 

0 - Warning 

 

1 - Shutdown 

 

2 - Electrical Trip 

Engine 

 

18 - Low DC Voltage Alarm 

0-25V (8V) 

19 - Charge Fail Voltage Alarm 

0-25V (8V) 

 

Fixed Input settings 

 

20 - Low Oil Pressure 

5-150PSI (15 PSI) 

21 - High Engine Temperature 

90-150 C (95 C) 

22 - Remote Start /  
Simulated Mains input 

0 - Remote start 
 close to activate 

 

1 - Remote start 
open to activate 

 

2 - Simulated mains 
close to activate 

 

3 - Simulated mains 
open to activate 

 

ACCESSING THE CONFIG EDITOR 

 

Press  the  Stop/Reset 

  and  Info 

  buttons 

simultaneously. 

 

The  LED  beside  the  AUTO  button  will 
flash  continuously  to  indicate  that 
configuration mode has been entered. 

 

 

The  first  configuration 
setting is displayed: 

 

From  the  configuration  table,  this  example  is 
displaying  Start  Delay  (parameter  0).  It  is  currently 
set to 5 seconds. 
 

EDITING A PARAMETER 

 

 

Enter the editor as described above. 

 

Press  +  /  -    to  scroll  through  the  parameters  to 
the one you want to change. 

 

Press 

  to  enter  edit 

mode.  The 

 

symbol 

will  flash  on  the  display 
to  indicate  that  edit 
mode has been entered.  

 

 

Press  +  /  -  to  change  the  value  to  the  desired 
parameter. 

 

Press 

 to save the value and exit edit mode for 

this parameter.  

 

The 

 

symbol will be removed from the display 

to indicate that edit mode has been exited.  

 

To  select  another  value  to  edit,  press  the  +  /  
buttons. Continuing to press the + and 

 buttons 

will  cycle  through  the  adjustable  parameters  as 
shown in the following lists. 

 
 

 

 
 

D E E P   S E A   E L E C T R O N I C S  

Model 720 Configuration and installation instructions 

 

 

053-005 
ISSUE 2 

NOTE: To exit the front panel configuration editor at any time, press the Stop/Reset 

 button. 

Ensure you have saved any changes you have made by pressing the 

 button first 

 

 

 

 

DIMENSIONS 

209mm x 146mm (8.23” x 5.75”)

 

MOUNTING 

Mounting holes suitable for 4 x 4mm screws 

Mounting Hole spacing 196.0mm x 103.5mm (7.717” x 4.075”)

 

PANEL CUT-OUT 

182mm x 137mm (7.17” x 5.39”)

 

Maximum panel thickness 

 

8mm (0.3”)

 

 

 

TYPICAL WIRING DIAGRAM 

Deep Sea Electronics Plc. 

Tel:+44 (0)1723 890099 

Fax: +44 (0)1723 893303 

LO CALL (from UK BT landlines) : 

Telephone 0845 260 8933 

Email: [email protected]  

Web: www.deepseaplc.com

 

Deep Sea Electronics inc. 

Phone: +1 (815) 316-8706 

Fax: +1 (815) 316- 8708 

TOLL FREE (USA only) : Tel: 1 866 636 9703  

Email: [email protected] 

Web: www.deepseausa.com

 

 

Deep Sea Electronics Plc. 

(Far East) 

Tel:+66 2 670 6228 

Fax: +66 2 678 3028 

Email: [email protected] 

Web: www.deepseaplc.com 

 

 

 

http://bestgenerator.spb.ru/?page_id=6765

Reviews: