8 Troubleshooting
8.1
Messages (Code type Bxx or Mxx)
In the event of failure, the control panel displays a message and a
corresponding code.
1. Make a note of the code displayed.
The code is important for the correct and rapid diagnosis of the
type of failure and for any technical assistance that may be
needed.
2. Switch the boiler off and switch back on.
The boiler starts up again automatically when the reason for the
blocking has been removed.
3. If the code is displayed again, correct the problem by following the
instructions in the table below:
Messages
Code Description
Checking / solution
BL.PSU ERROR
B00
The PSU PCB is incorrectly
configured
Parameter error on the PSU PCB
4
Set the type of generator again in the menu
#CONFIGURATION
(Refer to the original rating plate)
BL.MAX BOILER
B01
Maximum flow temperature
exceeded
The water flow in the installation is insufficient
4
Check the circulation (direction, pump, valves)
BL.HEATING
SPEED
B02
The increase in flow temperature
has exceeded its maximum limit
The water flow in the installation is insufficient
4
Check the circulation (direction, pump, valves)
4
Check the water pressure
4
Check the cleanliness of the heat exchanger
Sensor error
4
Check that the sensors are operating correctly
4
Check whether the boiler sensor has been correctly fitted
BL.DT OUTL RET. B07
Maximum difference between
the flow and return temperature
exceeded
The water flow in the installation is insufficient
4
Check the circulation (direction, pump, valves)
4
Check the water pressure
4
Check the cleanliness of the heat exchanger
Sensor error
4
Check that the sensors are operating correctly
4
Check whether the boiler sensor has been correctly fitted
BL.RL OPEN
B08
The
RL
inlet on the PCU PCB
terminal block is open
Parameter error
4
Set the type of generator again in the menu
#CONFIGURATION
(Refer to the original rating plate)
Bad connection
4
Check the wiring
BL.INV. L/N
B09
Set the type of generator again in the menu
#CONFIGURATION
(Refer to the original rating plate )
8. Troubleshooting
MCA 15 - MCA 25 MCA 25/28 MI
112
29/04/2010 - 300022146-001-B