6
GT 220 - GT 2200
22/01/09 - 300008281-001-E
2.
Description
2.4 Technical characteristics
12.5 % on fuel oil and 9.5 % on natural gas
- Flow temperature: 80 °C.
- Return temperature: 60 °C.
- Maximum operating pressure: 4 bar
- Maximum operating temperature: 100 °C
- Boiler thermostat setting: 30 - 90 °C
- Setting the safety thermostat: 110 °C
Boiler type
GT 224
GT 2204
160
GT 2204
250
GT 225
GT 2205
160
GT 2205
250
GT 226
GT 227
GT 228
Nominal output
Pn
kW
50
50
64
64
78
92
100
Useful output range
kW
40-50
40-50
50-64
50-64
64-78
78-92
92-100
Input range
kW
43.2-54.5
43.2-54.5
54.0-69.7
54.0-69.7
69.7-84.8
84.2-100.1 99.6-108.9
PCI efficiency - at 100% Pn
(Average temperature: 70 °C)
%
91.7
91.7
91.8
91.8
92.0
91.9
91.8
PCI efficiency - at 30% Pn
(Average temperature: 50 °C)
%
93.9
93.9
93.7
93.7
93.6
93.8
94.1
PCI efficiency - at 30% Pn
(Average temperature: 40 °C)
%
94.1
94.1
94.3
94.3
94.6
94.6
94.7
Fuel oil burner (Option)
1 stage
M200/1S(1) M200/1S(1) M200/1S(1) M200/1S(1) M201/2S
M201/2S
M201/2S
1 stage
M201/2N
M201/2N
M201/2N
M201/2N
2 stages
M202/2S(1) M202/2S(1) M202/2S(1)
1 stage (Belgium)
M100/3S
M100/3S
M100/3S(2) M100/3S(2)
1 stage
G200/1S
G200/1S
G200/1S
G200/1S
G200/1S(3)
Gas burner (Option)
1 stage
G201/2N(4) G201/2N
G201/2N
2-stage or modulating
G203/2N(4) G203/2N
G203/2N
Number of cast iron parts
4
4
5
5
6
7
8
Nominal water flow (Nominal output)
∆
T = 20K
m
3
/h
2.151
2.151
2.754
2.754
3.356
3.959
4.303
Stand-by losses
∆
T = 30K
W
197
197
213
213
226
238
247
Losses through the outer casing
∆
T = 30K
%
64
64
68
68
70
72
73
Auxiliary electrical power
( Nominal output - ex circulating pump)
W
10
10
10
10
10
10
10
Water content
litres
36
36
43
43
50
57
64
Water resistance
∆
T = 15K
mbar*
11.0
11.0
17.8
17.8
26.5
36.7
43.4
Flue gas circuit volume
litres
54
54
68
68
83
97
111
Combustion chamber
Inscribed Ø mm
309
309
309
309
309
309
309
Depth
mm
446
446
573
573
700
827
954
Volume
litres
33
33
42
42
51
60
69
Mass flue gas flow rate
Fuel oil
Kg/h
83
83
106
106
129
152
166
Gas
Kg/h
91
91
117
117
143
168
183
Pressure in the furnace for nozzle pressure = 0 mbar
mbar
0.2-0.5
0.2-0.5
0.3-0.6
0.3-0.6
0.3-0.8
0.4-0.8
0.6-0.9
Smoke temperature (Boiler temperature
=70 °C)
°C
<195
<195
<195
<195
<195
<205
<205
Weight (empty)
GT 220
kg
218
218
257
257
297
336
375
GT 2200
kg
318
348
357
387
-
-
-
Tank capacity
GT 2200
litres
160
250
160
250
-
-
-
Power exchanged
(5) (7)
GT
2200
kW
28
36
28
36
Specific flow **
(6) (7)
∆
T = 30K
litres per
min.
20.5
30
20.5
30
Flow per hour **
(6) (7)
∆
T = 35K
l/h
690
885
690
885
Flow in 10 minutes***
(6) (7)
∆
T = 30K
litres per
10 min.
255
385
255
385
Cooling constant Cr
Wh/
24h·L·K
0.26
0.23
0.26
0.23
Losses through the outer casing (DHW)
∆
T = 45K
kW
78
108
78
108
690
810
690
Auxiliary electrical power (DHW)
kW
80
80
80
80
255
385
255