5.4 Measured values and adjustment parameters
The regulator has a safety system that cuts off the tank at
temperatures of over 80°C.
Channel
Abbreviation
Range
Increment
Factory setting
Collector temperature
TC
[-50.0 ... 250.0] °C
-
-
Calorifier temperature
TS
[-50.0 ... 250.0] °C
-
-
Amount of heat
kWh
[0 ... 9999] kWh
-
-
Pump regime
PC
[0 ... 100] %
-
-
Self-calibration time
tc
[0 ... 5] minutes
-
-
Return temperature
TR
-50...250°C
-
-
Additional temperature
TM
-50...250°C
-
-
Type of installation
ANL
Installation 1
Installation 2
-
Installation 1
Temperature difference enabling the passage of the heating
return via the solar tank
DO
[0.5 ... 19.5] K
0.1
6
Temperature difference enabling heating return directly to the
boiler
DF
[0.4 ... 19.5] K
0.1
4
Reference temperature difference
DT
[10 ... 20] K
0.1
20
Zone changeover temperature (tank)
SZ
[20 ... 80] °C
0.1
55
Set temperature of the solar calorifier
SX
[20 ... 80] °C
0.1
60
Maximum collector temperature
CX
[100 ... 125] °C
0.1
100 °C
Self-calibration phase
tu
[1 ... 5] minutes
1
3
Pump minimum speed
PN
[20 ... 100] %
1
30
Pump command mode
POMP
OnOF / PuLS / PSOL
PSOL
Tubular solar collector function
FT
[0 ... 1]
1
0
Maximum flow rate
Fx
[0 … 20] l/min
0.1
Installation 1: 6.7
Installation 2: 4.2
Manual mode
MM
[0 ... 4]
1
4
Software version
VN
-
-
2.00
Measured values
Adjustment parameter