Code Faults
Cause
of the
fault
Description
Checking / solution
D17
DHW 2 S.FAIL
SCU
Sensor fault tank 2
Bad connection
4
Check whether the sensor is connected:
¼
See chapter: "Deletion of sensors from
the memory in the PCB", page 79
4
Check the link and the connectors
4
Check that the sensor has been correctly fitted
Sensor fault
4
Check the Ohmic value of the sensor
4
Replace the sensor if necessary
D27
PCU COM. FAIL
SCU
Communication failure between the SCU and PCU PCBs
4
Check the wiring between the SCU and PCU PCBs
4
Check that the PCU PCB is powered up (green LED on or flashing)
4
Change the PCU PCB
D32
5 RESET:ON/OFF
SCU
5 resets done in less than an hour
4
Switch the boiler off and switch back on
D37
TA-S SHORT-CIR
SCU
The Titan Active System® is short-circuited
4
Check that the connection cable between the SCU PCB and the anode is not short-
circuited
4
Check that the anode is not short-circuited
Remarks:
Domestic hot water production has stopped but can nonetheless be restarted using key
r
.
The tank is no longer protected.
If a tank without Titan Active System® is connected to the boiler,check that the TAS
simulation connector (delivered with package AD212) is fitted to the sensor card.
D38
TA-S DISCONNEC
SCU
The Titan Active System® is on an open circuit
4
Check that the connection cable between the SCU PCB and the anode is not severed
4
Check that the anode is not broken
Remarks:
Domestic hot water production has stopped but can nonetheless be restarted using key
r
.
The tank is no longer protected.
If a tank without Titan Active System® is connected to the boiler,check that the TAS
simulation connector (delivered with package AD212) is fitted to the sensor card.
7.4.1.
Deletion of sensors from the memory in the
PCB
The configuration of the sensors is memorised by the SCU PCB. If a
sensor fault appears whilst the corresponding sensor is not
connected or has been voluntarily removed, please delete the sensor
from the SCU PCB memory.
4
Press key
?
repeatedly until
Do you want to delete this
sensor?
is displayed
4
Select
YES
by turning the rotary button and press to confirm.
The outside temperature sensor cannot be deleted.
7. Troubleshooting
Diematic iSystem For C 330 / C 630 ECO
79
31082018 - 7600691-001-06