Code
Display text Description
Adjustment range
Subme
nu
280
350
430
500
570
650
PP007
Min anti-cy
cle time
Minimum heat generator
holding time that can be
reached after a stop
1 - 20 Min
Gas
fired ap
pliance
3
3
3
3
3
3
PP012
Stabilization
time
Stabilization time after
heat generator start for
central heating
0 - 180 Sec
Gas
fired ap
pliance
30
30
30
30
30
30
10.3.2 CU-GH13 control unit settings - C 640
All tables show the factory setting for the parameters.
Important
The tables also list parameters that are only applicable if the boiler
is combined with other equipment.
Tab.84 Navigation for basic installer level
Level
Menu path
Basic installer
> Installation Setup > CU-GH > Submenu
> Parameters, counters, signals > Parameters
(1) See the column "Submenu" in the following table for the correct navigation. The parameters are grouped in specific functionalities.
Tab.85 Factory settings at basic installer level
Code
Display text Description
Adjustment range
Subme
nu
560
700
860
1000 1140 1300
AP016
CH function
on
Enable central heating
heat demand processing
0 = Off
1 = On
Gas
fired ap
pliance
1
1
1
1
1
1
AP017
DHW func
tion on
Enable domestic hot water
heat demand processing
0 = Off
1 = On
Gas
fired ap
pliance
1
1
1
1
1
1
AP074
Force sum
mer mode
The heating is stopped.
Hot water is maintained.
Force Summer Mode
0 = Off
1 = On
Outdoor
tempera
ture
0
0
0
0
0
0
CP000
MaxZoneT
FlowSet
point
Maximum Flow Tempera
ture setpoint zone
7 - 100 °C
Direct
zone
80
80
80
80
80
80
CP010
Tflow set
point zone
Zone flow temperature
setpoint, used when the
zone is set to a fixed flow
setpoint.
7 - 100 °C
Direct
zone
90
90
90
90
90
90
CP080
User
T.Room Ac
tivity
Room setpoint tempera
ture of the user zone activ
ity
5 - 30 °C
Direct
zone
16
16
16
16
16
16
CP081
User
T.Room Ac
tivity
Room setpoint tempera
ture of the user zone activ
ity
5 - 30 °C
Direct
zone
16
16
16
16
16
16
CP082
User
T.Room Ac
tivity
Room setpoint tempera
ture of the user zone activ
ity
5 - 30 °C
Direct
zone
16
16
16
16
16
16
CP083
User
T.Room Ac
tivity
Room setpoint tempera
ture of the user zone activ
ity
5 - 30 °C
Direct
zone
16
16
16
16
16
16
CP084
User
T.Room Ac
tivity
Room setpoint tempera
ture of the user zone activ
ity
5 - 30 °C
Direct
zone
16
16
16
16
16
16
CP085
User
T.Room Ac
tivity
Room setpoint tempera
ture of the user zone activ
ity
5 - 30 °C
Direct
zone
16
16
16
16
16
16
10 Settings
96