Values at full load for G20 (H gas)
O
2
C 640 700
C 640 860
C 640 1000
C 640 1140
C 640 1300
(1) Nominal value
Tab.53 Checking/setting values for O
2
at full load for G25 (L gas)
Values at full load for G25 (L gas)
O
2
C 340 280
C 340 350
C 340 430
C 340 500
C 340 570
C 340 650
C 640 560
C 640 700
C 640 860
C 640 1000
C 640 1140
C 640 1300
(1) Nominal value
4. If the measured value is outside of the values given in the table,
correct the gas/air ratio.
5. Use the adjustment screw A to set the percentage of O
2
for the gas
type being used to the nominal value.
Increasing the gas flow, will decrease O
2
. The direction in which the
adjusting screw must be turned to increase or decrease the gas flow
is indicated on the gas control valve. The 5- to 9-section boilers are
supplied with a different gas control valve from the 10-section boiler.
See drawing for the position of adjusting screw A for full load.
6. Check the flame through the inspection glass. The flame must not
blow off.
Fig.71
Adjusting screw A
AD-0000492-01
O
A
A
3
7 Commissioning