Tab.113 Signals at advanced installer level
Code
Display text
Description
Range
Submenu
AM001
DHW active
Is the appliance currently in domestic hot
water production mode?
0 = Off
1 = On
Gas fired ap
pliance
AM011
Service required?
Is service currently required?
0 = No
1 = Yes
Gas fired ap
pliance
AM022
On / Off heat de
mand
On / Off heat demand
0 = Off
1 = On
Gas fired ap
pliance
AM024
Actual rel. Power
Actual relative power of the appliance
0 - 100 %
Gas fired ap
pliance
AM033
Next Service Ind.
Next service indication
0 = None
1 = A
2 = B
3 = C
4 = Custom
Gas fired ap
pliance
AM043
Pwr dwn reset nee
ded
A power down reset is needed
0 = No
1 = Yes
Gas fired ap
pliance
AP078
Out sensor detec
ted
Outside sensor detected in the applica
tion
0 = No
1 = Yes
Outdoor tem
perature
CM240
Zone Tout connec
ted
Outdoor temperature sensor is connec
ted to the zone
0 = No
1 = Yes
Direct zone
CM280
ZoneRTC Tcal
cRoomStp
Internal room temperature setpoint cal
culated by the room temperature control
ler of the zone
0 - 100 °C
Direct zone
GM006
GPS status
Gas Pressure Switch status
0 = Open
1 = Closed
2 = Off
Gas fired ap
pliance
GM012
Release Input
Release signal for the CU
0 = No
1 = Yes
Gas fired ap
pliance
GM013
Blocking Input
Blocking input status
0 = Open
1 = Closed
2 = Off
Gas fired ap
pliance
GM015
Vps Switch
Valve Proving System switch open /
closed
0 = Open
1 = Closed
2 = Off
Gas fired ap
pliance
PM003
ChTflowAverage
Actual average flow temperature
-25 - 125 °C
Gas fired ap
pliance
10.4.5 SCB-01 expansion PCB signals
Tab.114 Navigation for basic installer level
Level
Menu path
Basic installer
> Installation Setup > SCB-01 > Submenu
> Parameters, counters, signals > Signals
(1) See the column "Submenu" in the following table for the correct navigation. The signals are grouped in specific functionalities.
Tab.115 Signals at basic installer level
Code
Display text
Description
Range
Submenu
AM010
Pump speed
The current pump speed
0 % - 100 %
0-10 volt or
PWM out
AM012
Status Appliance
Current main status of the appliance.
See
System
Functionality
AM014
Sub status
Appliance
Current sub status of the appliance.
See
System
Functionality