![DeDietrich C 340 280 Installation And User Manual Download Page 114](http://html1.mh-extra.com/html/dedietrich/c-340-280/c-340-280_installation-and-user-manual_2462417114.webp)
Code
Display text
Description
Range
Submenu
Default
setting
CP800
CP801
CP802
CP803
CP804
Commercial Dhw
Mode
Select the requested heating mode
for commercial domestical hot water
tank
0 = Preheat
1 = Heating
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
0
0
0
0
0
CP810
CP811
CP812
CP813
CP814
DHW Backup
Capacity
Total electrical backup capacity
available to heat DHW tank
1 kW - 255 kW
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
12
12
12
12
12
CP820
CP821
CP822
CP823
CP824
DHW Production
Time
Maximum reserved time for complete
charging of the tank
1 HoursMinutes - 120
HoursMinutes
CIRCA 1
CIRCB 1
DHW 1
CIRCC 1
AUX 1
60
60
60
60
60
EP036
EP037
Sensor input
config
Sets the general configuration of the
sensor input
0 = Disabled
1 = DHW tank
2 = DHW tank top
3 = Buffer tank sensor
4 = Buffer Tank top
5 = System (cascade)
Analogue
input
0
NP001
CascProdMan
Hys.High
Hysterese high for Producer Manager 0.5 °C - 10 °C
Cascade
management
B
3
NP002
CascProdMan
Hys.Low
Hysterese low for Producer Manager 0.5 °C - 10 °C
Cascade
management
B
3
NP003
CascProdManErr
Range
Maximum error gain for Producer
Manager
0 °C - 10 °C
Cascade
management
B
10
NP004
CascPFactorAlgo
Temp
Proportional Factor for cascade with
Temperature algorithm
0 - 10
Cascade
management
B
1
10.4 List of measured values
10.4.1 Control unit counters
Tab.98 Navigation for basic installer level
Level
Menu path
Basic installer
> Installation Setup > CU-GH13 > Submenu
> Parameters, counters, signals > Counters
(1) See the column "Submenu" in the following table for the correct navigation. The counters are grouped in specific functionalities.
Tab.99 Counters at basic installer level
Code
Display text
Description
Range
Submenu
AC001
Hours on mains
Number of hours that the appliance has
been on mains power
0 - 4294967295 Hours
System Func
tionality
AC002
Service run hours
Number of hours that the appliance has
been producing energy since last service
0 - 131070 Hours
Gas fired ap
pliance
AC003
Hours since service Number of hours since the previous
servicing of the appliance
0 - 131070 Hours
Gas fired ap
pliance
AC004
Starts since service Number of heat generator starts since
the previous servicing.
0 - 4294967295
Gas fired ap
pliance
10 Settings
114
C 340 / C 640
7762666 - v.02 - 29092020