Code
Display text Description
Adjustment range
Subme
nu
560
700
860
1000 1140 1300
DP020
Postrun
DHW
pump/3wv
Post run time of the DHW
pump/3 way valve after
DHW production
0 - 99 Sec
Gas
fired ap
pliance
10
10
10
10
10
10
DP140
DHW load
type
DHW load type (0 : Combi,
1 : Solo)
0 = Combi
1 = Solo
2 = Layered cylin
der
3 = Process heat
4 = External
Gas
fired ap
pliance
1
1
1
1
1
1
GP010
GPS Check Gas Pressure Switch
check on/off
0 = No
1 = Yes
Gas
fired ap
pliance
1
1
1
1
1
1
GP017
Max power
Maximum power percent
age in kilo Watt
0 - 1000 kW
Gas
fired ap
pliance
294,
2
351,
2
425,
6
494,
7
564,
4
642
GP022
Tfa Filter
Tau
Tau factor for average flow
temperature calculation
0 - 255
Gas
fired ap
pliance
1
1
1
1
1
1
GP042
Fan RPM
Max
Maximum fan speed
0 - 65535 Rpm
GVC
Pneu
matic
5700 5800 3700 4000 4500 4300
GP050
Power Min
Minimum power in kilo
Watt for RT2012 calcula
tion
0 - 300 kW
Gas
fired ap
pliance
80
111
142
141
170
180
PP007
Min anti-cy
cle time
Minimum heat generator
holding time that can be
reached after a stop
1 - 20 Min
Gas
fired ap
pliance
3
3
3
3
3
3
PP012
Stabilization
time
Stabilization time after
heat generator start for
central heating
0 - 180 Sec
Gas
fired ap
pliance
30
30
30
30
30
30
10.3.3 SCB-01 expansion PCB settings
Tab.90 Navigation for installer level
Level
Menu path
Installer
> Installation Setup > SCB-01 > Submenu
> Parameters, counters, signals > Parameters
(1) See the column "Submenu" in the following table for the correct navigation. The parameters are grouped in specific functionalities.
10 Settings
102