DeDietrich 100012532 Technical Information Download Page 1

QM

1 / 2

IT2673A

TI

Technical information

Heat pumps

Outdoor units AWHP... - All powers

Option Electrical tracing kit (Heating cord)

Package EH113

01.45.91.56.02 – G.CHAMPION /J. SCHALCK

N° IT2673A

-en

20/06/2018

EN

SUSTAINABLE COMFORT®

1. Purpose

On the field, we noticed that the installation of the heating cord (EH113) does not comply with our recommendations
and the rules of the art. These non-compliances led to fire starts.

Therefore, and for safety reasons, we ask you to check the whole installed product park, during the mandatory
annual maintenance.

2. Accessories concerned

100012532 - Condensate container for wall bracket (Package EH111)

100012534 - Electrical tracing kit (Package EH113)

3. Main checkings

3.1

Thoroughly inspect the condition of the cord:

Check if the heating cord is not damaged (bare or cut), if it has not been damaged by rodents,...

- Only qualified professionals are authorised to work on the appliance and the
installation.
- Before any intervention, ensure compliance with safety standards (including the
grounding of metal pipes in accordance with the professional standards).
- Any manipulation of the heating cord must be done with the power OFF !
- Follow the instructions hereafter to avoid any risk of overheating and fire !
- It is strictly forbidden to modify the structure of the electric heating cord !

Remove the cord if it is damaged !

Reviews: