![DECODE EMU Series User Manual Download Page 13](http://html.mh-extra.com/html/decode/emu-series/emu-series_user-manual_2461817013.webp)
EMU - User manual v1.2
Technical characteristics
6 Technical characteristics
6.1 Common characteristics of EMU V3, C3, A3
Number of inputs
3
Communication
Modbus slave, RS-485, address range 1-247,
broadcast address 0
Serial speed
1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
Data format
1 start, 8 data, parity: None, Even, Odd
Factory defaults
9600bps, 1 start, 8 data, parity none, Modbus address 1
Connection
Screw terminals
Power supply
10-28V DC
Consumption
less than 1W
Enclosure
Plastic, DIN 35mm rail mounting
Dimensions
35 x 88 x 57 mm
Isolation
3000V DC
6.2 EMU V3 – Three phase AC voltage
Measured parameters
AC voltage L1, L2, L3, L12, L23, L31, frequency
Measurement type
True RMS, frequency is measured indirectly by measuring
the signal period
Measurement range
L1, L2, L3 0-250V AC rms
L12, L23, L31 0-500V AC rms
Frequency 20-70Hz
Resolution
Voltage 10mV rms
Frequency 0.01Hz
6.3 EMU C3 - Three phase AC current, with CT*
Measured parameters
AC current CT1, CT2, CT3
Measurement type
True RMS
Measurement range
0-5A AC rms
Resolution
Current 1mA rms
Frequency 0.01Hz
* Must be used with current transformers (CT) with 5A output.
www.decode.rs
13/15
EMU_UM_V12_05042020.pdf