background image

- 1 -

100.6015.10

Instruction Manual — Series 200
Remote Meter Panels 500 PPD 
(10 kg/h) Maximum Capacity

100 PPD (2 kg/h) Maximum

200 PPD (4 kg/h) Maximum 

(250 PPD [5 kg/h] Chlorine only)

500 PPD (10 kg/h) Maximum

Summary of Contents for 200 Series

Page 1: ... 1 100 6015 10 Instruction Manual Series 200 Remote Meter Panels 500 PPD 10 kg h Maximum Capacity 100 PPD 2 kg h Maximum 200 PPD 4 kg h Maximum 250 PPD 5 kg h Chlorine only 500 PPD 10 kg h Maximum ...

Page 2: ...to instruction operating manuals all instructions given on labels or attached tags should be followed Regardless of these efforts it is not possible to eliminate all hazards from the equipment or foresee every possible hazard that may occur It is the responsibility of the installer to ensure that the recommended installation instructions are followed It is the responsibility of the user to ensure ...

Page 3: ... 4 SERVICE 12 4 1 Cleaning the Flowmeter Assembly 12 4 2 Rate Adjustment Valve Cleaning 12 5 TROUBLESHOOTING CHART 13 FIGURES 1 100 PPD 2 kg h Meter Panel 6 2 200 PPD 4 kg h 250 PPD 5 kg h Chlorine only Meter Panel 7 3 500 PPD 10 kg h Meter Panel 8 4 100 PPD 2 kg h Meter Panel Components 9 5 250 PPD Max 4 kg h Meter Panel Components 10 6 500 PPD 10 kg h Meter Panel Components 11 ...

Page 4: ...nd quantity of the gas being handled 2 the complexity of the gas supply system 3 the quality and quantity of water or process liquid being used to operate the ejector s and 4 operation procedures More frequent service periods are especially indicated when venting of the VR is occurring during the one year operational period This is usually indicative of foreign debris holding the inlet valve open ...

Page 5: ...er panel If the surface is not suitable for wood screws choose an appropriate anchor bolt to that surface Black polyethylene tubing is normally used for the vacuum line Do not kink this tubing It may be desirable to use tubing connectors tees or 90 elbows to provide as direct run as possible and minimize kinking conditions Use enough tubing length to allow movement of the vacuum regulator for serv...

Page 6: ...100 6015 10 6 Figure 1 100 PPD 2 kg h Meter Panel ...

Page 7: ... 7 100 6015 10 Figure 2 200 PPD 4 kg h Meter Panel ...

Page 8: ... feeding sulfur dioxide the actual flow rate is 0 95 of the scale value For example a reading of 50 PPD 1 kg h is actually 45 PPD 0 95 kg h sulfur dioxide If feeding ammonia the actual flow rate is 0 50 of the scale value For example a reading of 50 PPD 1 kg h is actually 25 PPD 0 5 kg h ammonia Read the flowmeter scale at the center of the ball NOTE NEVER use the rate valve on the remote meter pa...

Page 9: ... 9 100 6015 10 Figure 4 100 PPD 2 kg h Meter Panel Components ...

Page 10: ...100 6015 10 10 Figure 5 250 PPD Max 4 kg h Meter Panel Components ...

Page 11: ... 11 100 6015 10 Figure 6 300 6 kg h 500 PPD 10 kg h Meter Panel Components ...

Page 12: ...n the metering ball using wood alcohol and rinse thoroughly with warm water 4 1 6 Thoroughly dry the glass metering tube Reassemble the metering stops and ball 4 1 7 Reinstall the meter assembly by tightening the meter inlet plug making sure that it is on center with the top and bottom gasket NOTE The meter gaskets can usually be reused Turn the gaskets over for best results 4 2 Rate Valve Cleanin...

Page 13: ...onnection and remake as necessary c Replace vacuum tubing and arrange line s to eliminate 2 Flowmeter ball bounces and or maximum gas feed rate cannot be achieved during normal operation a Vacuum regulator inlet filter screen dirty b Rate valve dirty c Flowmeter dirty d Ejector water supply pressure fluctuating causing insufficient ejector vacuum Ball bouncing only a Replace gas inlet filter b Cle...

Page 14: ... improvements may be made without notice SEP 2015 De Nora Water Technologies 3000 Advance Lane Colmar PA 18915 ph 1 215 997 4000 fax 1 215 997 4062 web www denora com mail info dnwt denora com Registered Trademark 2015 All Rights Reserved ...