6. Settings
Programming emergency position for 0…10 VDC control signal
When the 0…10 VDC control signal fails (= 0 VDC), the KL300 will automatically move to the emergency
position. To apply the emergency position, next requirements need to be met:
• Control signal needs to be in the range of 1…10 VDC.
• The emergency position needs to be set.
• The control signal fails for at least 45 seconds (alarm delay).
To set the emergency position the following steps need to be taken:
1. Both endpositions of the KL300 must be set and the operating mode is active.
2. Set the climate controller to a position that meets the desired emergency position.
3. When the KL300 has reached the desired position LED’s “I” or “II” stop flashing.
4. Press both buttons “I” and “II” simultaneously for minimal 5 seconds. The LED’s “I” and “II” will flash.
5. Press button “OK” to set the emergency position.
Note
To remove the emergency position press both buttons “I” and “II” simultaneously for minimal 5 seconds
again. Then switch off the 24 VDC power.
Led indication
Step Action
OK
I
II
Description
1
Both endpositions have been programmed and the operating mode is active
(ON)
(OFF)
(OFF)
KL300 is between
endpositions “I” and “II”
Or
(ON)
(ON)
(OFF)
KL300 is in endposition
direction “I”
Or
(ON)
(OFF)
(ON)
KL300 is in endposition
direction “II”
2
Set climate controller to
emergency position
(ON)
(OFF)
KL300 moves in direction “I”
to emergency position
Or
(ON)
(OFF)
KL300 moves in direction “II”
to emergency position
3
KL300 has reached desired
emergency position
(ON)
(OFF)
(OFF)
Ready to set emergency
position
4
Press “I” and “II” simultaneously
for 5 sec.
(ON)
5
Press “OK” to set emergency
positon
See section 13 for explanation of the sumbols of the LED flashing patterns