Category
Parameter
Description
Possible values
Default value
Length
(in bits)
DEVICE
LED_BUZZER_ENABLE
Flag to enable/disable
LED and Buzzer
interactions for action
not triggered by the
button.
0b0 = false, LEDs are
OFF
0b1 = true, LEDs are
ON
0b0 = false
1
DEVICE
DEVICE_RESET
Once this parameter
is set, the device
shall restart once
after having received
the DL.
0b1010 = 0xA =
Force device reset
others = do nothing
others = do nothing
4
DEVICE
TX_REPEAT
Number of Sigfox
frames
0b0 = 1 frames
0b1 = 3 frames
0b0 = 1 frames
1
HEARTBEAT
HEARTBEAT_PERIOD
Period of time to send
HEARTBEAT event
0b000 = every 1h
0b001 = every 6h
0b010 = every 12h
0b011 = every 24h (1
day)
0b100 = every 48h (2
day)
0b101 = every 72h (3
day)
0b110 = every 120h
(5 day)
0b111 = every 240h
(10 day)
0b100= every 48h (2
days)
3
NH3
NH3_ENABLE
Enable NH3 sensing
0b0 = false, NH3
sensing is disabled
0b1 = true, NH3
sensing is enabled
0b1 = true
1
NH3
NH3_MEASURE_PERIOD
Interval of time
between two
consecutive NH3
values are acquired
0b0000 = every 1s
0b0001 = every 2s
0b0010 = every 5s
0b0011 = every 10s
0b0100 = every 20s
0b0101 = every 30s
0b0110 = every 1min
0b0111 = every 2min
0b1000 = every 5min
0b1001 = every
10min
0b1010 = every
20min
0b1011 = every
30min
0b1100 = every 1h
0b1101 = every 2h
0b1110 = every 3h
0b1111 = every 6h
0b0010 = every 5s
4
NH3
NH3_EVENT_ENABLE
Enable NH3 event
0b0 = false, NH3
event is disabled
0b1 = true, NH3
event is enabled
0b1 = true
1
NH3
NH3_EVENT_PERIOD
Interval of time
between two
consecutive NH3
events
0b000 = every
10min
0b001 = every
30min
0b010 = every 1h
0b011 = every 2h
0b100 = every 3h
0b101 = every 6h
0b110 = every 12h
0b111 = every 24h
0b010 = every 1h
3
5.7 Configuration Parameters