Modbus
Register
Hex address
# of Registers
Description
Range
Default
Format
Property
395
18B
1
RSSI threshold
to detect
(-100)-0
-60
uint16
Read/Write
396
18C
1
ASCII send
cycle (second)
1-3600
300
uint16
Read/Write
397
18D
1
ASCII send
enable
0-1
1
uint16
Read/Write
The WS433-TAG will send the signal to WS433-CL-07 every 60 seconds (default setting).
WS433-CL-07 sends data back to the black box according to the ASCII send_cycle configured time cycle, the default
setting is 300 seconds.
- When [error code] = 1 means that WS433-CL-07 has no wireless sensor tag connected yet.
- When the WS433-CL-07 is not connected to the WS433-TAG, if there is a sensor tag nearby, it will sends all 3 packets
with RSSI > RSSI threshold, the WS433-CL-07 receives that sensor tag and [error code] = 0, the buzzer of WS433-
CL-07 will beep once.
- When the WS433-CL-07 is not connected to the WS433-TAG, If there are ≥2 nearby sensor tags, the WS433-CL-07 will
receive the sensor tag which has the largest RSSI.
- When [error code] = 0 means that WS433-CL-07 has connected to a sensor tag. At that moment, WS433-CL-07 will
lock this sensor tag, not accept other sensor tag even if that sensor tag has a bigger RSSI.
- When [error code] = 0 means that WS433-CL-07 has connected to a certain sensor tag. If within 5 minutes, this
sensor tag is separated and not sent back to the WS433-CL-07. Then [error code] = 1 and WS433-CL-07 will return to
the state with no sensor tag connected, then ready to connect to a new nearby sensor tag.
Red:
PWR+(7...48VDC)
Black: PWR-(0VDC)
4.4 Datagram from Tx pin of RS232 port:
DV,[Sensor Type],[ID Sensor tag],[% sensor battery],[RF signal strength],[error code],[value 1],
[value 2],[Checksum][\r\n]
5. Operation Principle of WS433-CL-07
5.1 IO Wiring
Each cable includes wires which are marked labels according to types of connection. (user should not cut these
labels before installation to avoid confusion).
The signal wire Tx (WS433-CL-07) will connect to the Rx (Black box) wire and vice versa.