32
7.2
Output module register address information: 0x2000–
0x20F6 (rewritable)
I.
Rewrite a digital output register
GFDO-RM01N (16 bit, sink type)/ GFDO-RM02N (16 bit, source type)
register format
Channel open-1; channel closed - 0; reserved value - 0.
Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit9
Bit8
Ch44 Ch43 Ch42 Ch41 Ch34 Ch33 Ch32 Ch31
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
Ch24 Ch23 Ch22 Ch21 Ch14 Ch13 Ch12 Ch11
Example:
With all channels open: 1111 1111 1111 1111 (0xFF 0xFF).
Channel 1 to 8 are open:0000 0000 1111 1111 (0x00 0xFF).
With all channels closed: 0000 0000 0000 0000 (0x00 0x00).
III.
Rewrite an analog output register
Once an analog output module is set up with a control module, it will
automatically assign analog output modules’ output records registers between
0x2000 and 0x2003