DAUDIN iO-Grid GFPS-0202 Manual Download Page 6

 

 

 

 

 

3.

 

Power Module Information 

3.1

 

Power Module Dimensions 

I.

 

GFPS-0202 

 

 

 

Unit: mm 

Summary of Contents for iO-Grid GFPS-0202

Page 1: ...iO GRID M Power Module User Manual 2211TW V2 0 0 ...

Page 2: ...formation 6 3 1 Power Module Dimensions 6 3 2 Power Module Panel Information 8 4 Module Installation Disassembly 10 4 1 Installation 10 4 2 Removal 11 5 iO GRID M Series Introduction 12 5 1 iO GRID M Components 12 6 Power Module Instructions 13 6 1 Power Module Assembly and Connections 13 6 2 Power Module Insulation Map 15 ...

Page 3: ...3 1 Power Module List Product No Description Remarks GFPS 0202 100 240 VAC to 24 VDC Power Module GFPS 0303 24 VDC to 5 VDC Power Module ...

Page 4: ...Overload 120 185 Rated Output Power Overvoltage Protection Clamper Overvoltage Protection Overvoltage 30 34 VDC General Specification Dimension W D H 20 x 100 x 96mm Weight 126g Ambient Temperature Operation 20 60 Ambient Humidity RH 20 90 Altitude Limit 2000 m Ingress Protection IP IP 20 Pollution Severity II Safety Approval CE Wiring Range IEC UL 0 2 mm 2 5 mm AWG 26 12 Wiring Ferrules DN00508D ...

Page 5: ...mper Overvoltage Protection Latching Overload 127 170 Rated Output Power Overvoltage Protection Clamper Overvoltage Protection Overvoltage 6 5 VDC 6 7 VDC General Specification Dimension W D H 12 x 100 x 96mm Weight 68g Ambient Temperature Operation 20 60 Ambient Humidity RH 20 90 Altitude Limit 2000 m Ingress Protection IP IP 20 Pollution Severity II Safety Approval CE ...

Page 6: ...6 3 Power Module Information 3 1 Power Module Dimensions I GFPS 0202 Unit mm ...

Page 7: ...7 II GFPS 0303 Unit mm ...

Page 8: ...8 3 2 Power Module Panel Information I GFPS 0202 LED Indicator Light LED Color Status DC24V 2A Green Power Conve Rterrunning ...

Page 9: ...9 I GFPS 0303 LED Indicator Light LED Color Status DC5V 4A Green Power Converter Running ...

Page 10: ...le to the arrow on the DIN rail II Press the module down and the metal clamp will slide thanks to its spring mechanism and grab on the other side of the DIN rail Continue to push down until the metal clamp clicks Note Make sure the red arrows on the module and the rail are pointing the same direction ...

Page 11: ...11 4 2 Removal I Use a screwdriver to pull the metal hook sideways and detach the module from the DIN rail II Remove all modules from the DIN rail in reverse order of installation ...

Page 12: ...bus TCP Please choose products and factory controllers to figure your system based on your communication protocol 5 1 iO GRID M Components I DINKLE Bus Rail 1 to 4 are defined for power supply and rail 5 and 7 are defined for communication DINKLE Bus Rail Definitions Rail Definition Rail Definition 8 4 0V 7 RS485B 3 5V 6 2 0V 5 RS485A 1 24V ...

Page 13: ... Module Assembly and Connections I Install the fieldbus to the DIN rail II Install GFPS 0202 to the fieldbus and GFPS 0202 will convert the alternating current from the external power supply into 24V direct current and feed it to the fieldbus ...

Page 14: ...ldbus and GFPS 0303 will convert the 24V direct current from the fieldbus into 5V direct current before feeding it to the fieldbus IV Plug the external alternating current power supply to the L N and G connectors on GFPS 0202 accordingly ...

Page 15: ...15 6 2 Power Module Insulation Map I GFPS 0202 ...

Page 16: ...16 II GFPS 0303 ...