3 of 4
Network Settings.
1. Modify the network settings.
2. Click Save to save the new Network settings.
The IP address must be unique to the network.
Setting a 4-20mA Output.
1. Under the Output Type select 20 mA.
2. Under value type 4 mA.
3. Click Write Ch0.
4. Check the mA output on Terminal 1 and 2.
5. You can also enter an amount in Safe and
power-up and click Write CH0.
6. Recycling the power will check these func-
tions.
Setting a 0-10 Volt Output.
1. Under the Output type select 10V.
2. Under Value type 10V.
3. Click Write Ch0.
4. Check the Voltage output on Terminal 3 and
4.
5. You can also enter a value in the Safe and
power-up modes and cklick Write CH0.
6. Recycling the power will check these func-
tions.
Each channel may be different to the other
channels, Channel 1 could be mA output and
Channel 0, 2, and 3 could be voltage Output. All
channels are isolated from each other, the Power
Supply and the Modbus TCP.