CONFIGURATION BY PC

By software DATESOFT it is possible to:
- set the default programming of the device;
- program the options not available with the dip-switch;
  (burn-out level, etc...);
- read, in real time, the input and output measures;
- follow the dip-switches configuration wizard.

To configure the device follow the next steps:
1) Power-on the device.
2) Open the protection plastic label on the front of the device. 
3) Connect the interface PRODAT to the PC (COM port)
    and to the device (PGRM connector).
4) Open DATESOFT.
5) Select the COM port in use.
6) Click on “Open COM”.
7) Click on “Program”.
8) Set the programming data.
9) Click on “Write” to send the programming data to the device.

Warning: during these operations the device must always be powered and the TX/RX cable always connected.
For information about DATESOFT refer to the software's user guide.

DIP-SWITCH CONFIGURATION TABLES

PROGRAMMING

J

1

TX/RX CABLE

PRODAT

COM PORT

P.C.

V+ V-

Q

R

PGRM

Plastic label protection

DAT

POWER SUPPLY

UNIT

1) Open the suitable door on the side of the device. 

2) Set the input type by the dip-switch SW1 [1..4] (see TAB.1)

3) Set the minimum input scale value (Zero)  by the dip-switch SW1 [5..8] (see TAB.3)

4) Set the maximum input value (Full scale) by the dip-switch SW2 [1..6] (see TAB.3)

5) Set the output type by the dip-switch SW2 [7..8] (see TAB.2)

NOTE:
- It is also possible to set the dip-switches using the wizard of the configuration software following the procedure described in the section ”Configuration by 
PC” until the step 6 and clicking on “Switch”.

CONFIGURATION BY DIP-SWITCHES

8

7

6

5

4

3

2

1

8

7

6

5

4

3

2

1

SW1

SW2

 Input type

Output

Full scale

Zero

OFF

ON

NOTES:

* For all the input type selected by dip-switches, the compensation of wires is 

fixed at 3.

* To configure the range for the input type selected (TAB.1) refer to the section 

of the TAB.3 on next page relative to it (ex: for Pt100 use the table TAB.3c ).

*  If the dip-switches SW1 [1..4] are  all  set in the   position 0 (“EPROM”),  the 

device will follow the configuration programmed by PC ( input type and range, 
output type and range and options).

*  If  the  dip-switches  SW1  [5..8]  are  all  set  in  the    position  0  (“Default”),  the 

device  will  follow  the  input  scale  programmed  by  PC  for  the  input  type 
selected by the dip-switches SW1 [1..4]

*  Eventual wrong  dip-switches  settings  will  be signalled by the blinking of  the 

led “PWR”.

0-20 mA

SW2

8

7

TAB.2
Output settings

4-20 mA

0-10 V

0-5 V

SW1

3

2

1

EPROM *

TAB.1
Input type settings

R 2K

Pt100

Ni100

Pt1000

Ni1000

R 500

4

SW1

3

2

1

---

4

---

---

---

---

---

---

---

---

- Input type 

Pt100

- Zero value 

-50 °C

- Full scale value

200 °C

- Output type 

4-20 mA

EX. of configuration:

SW1 =

SW2 =

Summary of Contents for DAT 4631 B

Page 1: ...tandards USER INSTRUCTIONS The converter must be powered by a direct voltage applied to the terminals Q and R The analog channel measures the value from the sensor connected to the terminals the I L and G and transmits the output measures on the terminals N and M OUT A and the terminals P and O OUT B The input and output connections must be made as shown in the section Connections It is possible t...

Page 2: ...alue Full scale by the dip switch SW2 1 6 see TAB 3 5 Set the output type by the dip switch SW2 7 8 see TAB 2 NOTE It is also possible to set the dip switches using the wizard of the configuration software following the procedure described in the section Configuration by PC until the step 6 and clicking on Switch CONFIGURATION BY DIP SWITCHES 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 SW1 SW2 Input type Outp...

Page 3: ... 2 1 Default 50 55 60 65 70 75 80 85 90 95 100 110 115 120 Ω 5 6 SW2 4 3 2 1 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 5 6 SW2 4 3 2 1 220 230 240 250 260 270 280 290 300 310 320 330 340 350 5 6 SW2 4 3 2 1 380 390 400 5 6 410 420 430 440 450 460 470 500 500 30 20 200 360 480 490 500 370 210 105 Ω Ω Ω TAB 3b Settings for Resistance 500 ohm Zero SW1 8 7 6 5 Default 200 150 40 30 2...

Page 4: ...se of high power supply value 27 Vdc Use of output current Make sure that sufficient air flow is provided for the device avoiding to place raceways or other objects which could obstruct the ventilation slits Moreover it is suggested to avoid that devices are mounted above appliances generating heat their ideal place should be in the lower part of the panel Install the device in a place without vib...

Reviews: