DAT 4631 B

DAT 4631 B

Isolated Doubler / Converter

 for RTD and resistance 

configurable by Dip-Switch or PC

FEATURES
- Configurable input for RTD and resistance
- Double output configurable in current or voltage
- Configurable by dip-switch or PC
- High accuracy
- On-field reconfigurable
- Galvanic isolation among the ways
- EMC compliant – CE mark
- Suitable for DIN rail mounting in compliance       
  with EN-50022 and EN-50035

GENERAL DESCRIPTION

The isolated doubler/converter DAT 4631 B is able to measure and linearise the standard RTDs and resistances with 2 or 3 wires cable compensation . 
In function of programming, the measured values are converted in a current or voltage signal. The device guarantees high accuracy and performances 
stability  both versus time and temperature.
The programming is made by the dip-switch located in the window on the side of the enclosure. By means of dip-switches it is possible to select the input 
type and range and the output type without recalibrate the device.
Moreover, by Personal Computer the user can program all of the device's parameters for his own necessity;  the configuration by PC allows to program 
the two outputs with two independent settings. For all the sensors it is possible to set the cable compensation with 2 or 3 wires.
Moreover it is available the option of alarm for signal interruption (burn-out) that allows to set the output value as high or low out of scale .
The 1500 Vac galvanic isolation on all ways (input, outputs and power supply) eliminates the effects of all ground loops eventually existing and allows the 
use of the converter in heavy environmental conditions found in industrial applications.
The DAT 4631 B is in compliance with the Directive 2004/108/EC on the Electromagnetic Compatibility.
It is housed in a plastic enclosure of 12.5 mm thickness suitable for DIN rail mounting in compliance with EN-50022 and EN-50035 standards.

USER INSTRUCTIONS

The converter must be powered by a direct voltage applied to the terminals Q and R.
The analog channel measures the value from the sensor connected to the terminals the I, L and G and transmits the output measures on the terminals N 
and M (OUT A) and the terminals P and O (OUT B).
The input and output connections must be made as shown in the section "Connections".  
It is possible to configure the converter on field by dip-switch or Personal Computer as shown in the section “ Programming ". The configuration by dip-
switches can be made also if the device is powered (note: after the configuration the device takes some seconds to provide the right output measure ).

TECHNICAL SPECIFICATIONS (Typical at 25 °C and in nominal conditions)

Sensor excitation current

RTD,Res

500 uA

Line resistance influence 

(1)

RTD 3 wires           0.05%/

 (50 

 max balanced)

Linearity 

(1)

RTD

± 0.1 % f.s. 

Thermal drift 

(1)

Full scale 

± 0.01% / °C

Input type

  Min

  Max

Min.Span 

TEMPERATURE AND HUMIDITY

Operative temperature

-20°C .. +60°C

Storage temperature              -40°C.. +85°C
Humidity (not condensed)

0 .. 90 %

Output type

 

Min

  Max

Min Span 

HOUSING

Material                Self-extinguishing plastic
Mounting                DIN rail in compliance 

with EN-50022 and 

                               EN-50035 
Weight

about 90 g.

Output calibration

Current

± 7 uA

Voltage

± 5 mV

Power supply voltage

18 .. 30 Vdc

Reverse polarity protection

60 Vdc max

EMC ( for industrial environments )

Immunity                 

EN 61000-6-2

Emission                 

EN 61000-6-4

Current consumption 

Current output

55 mA max.

Voltage output

25 mA max.

Burn-out values

Max. output value   

 22 mA or 10.6 V

Min. output value     

 0 mA or -0.6 V

Current

 0 mA

20 mA

  4 mA

Voltage 

 0  V

10  V

  1  V

(1)referred to the input Span (difference between  max. and min.)

Response time 

(10÷ 90%) 

about 

 

500 ms

Output load Resistance - Rload

 

Current output

< 500 

Voltage output

> 10 K

Short circuit current                26 mA max.

ISOLATION

Among all ways

         

1500 Vac,
50 Hz, 1 min

POWER SUPPLY

INPUT 

OUTPUT (2 CHANNELS) 

RTD 

(

2, 3 wires)

Pt100

-200°C

850°C

   50°C

Pt1000

  -85°C

185°C

   30°C

Ni100

  -60°C

180°C

   50°C

Ni1000

  -60°C

150°C

   30°C

RES.

 

(2, 3 wires)

    

 0 

  500 

   50 

    

 0 

2000 

   50 

Input Calibration 

(1)

RTD

            the higher of ±0.1% and ±0.2°C

Low Res.             the higher of ±0.1% and ±0.15 

High Res.            the higher of ±0.2% and ± 1 

RTD/RES 
   

V

mA

V

mA

DC SUPPLY

OUTPUT A

+

-

INPUT

OUTPUT B

Summary of Contents for DAT 4631 B

Page 1: ...tandards USER INSTRUCTIONS The converter must be powered by a direct voltage applied to the terminals Q and R The analog channel measures the value from the sensor connected to the terminals the I L and G and transmits the output measures on the terminals N and M OUT A and the terminals P and O OUT B The input and output connections must be made as shown in the section Connections It is possible t...

Page 2: ...alue Full scale by the dip switch SW2 1 6 see TAB 3 5 Set the output type by the dip switch SW2 7 8 see TAB 2 NOTE It is also possible to set the dip switches using the wizard of the configuration software following the procedure described in the section Configuration by PC until the step 6 and clicking on Switch CONFIGURATION BY DIP SWITCHES 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 SW1 SW2 Input type Outp...

Page 3: ... 2 1 Default 50 55 60 65 70 75 80 85 90 95 100 110 115 120 Ω 5 6 SW2 4 3 2 1 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 5 6 SW2 4 3 2 1 220 230 240 250 260 270 280 290 300 310 320 330 340 350 5 6 SW2 4 3 2 1 380 390 400 5 6 410 420 430 440 450 460 470 500 500 30 20 200 360 480 490 500 370 210 105 Ω Ω Ω TAB 3b Settings for Resistance 500 ohm Zero SW1 8 7 6 5 Default 200 150 40 30 2...

Page 4: ...se of high power supply value 27 Vdc Use of output current Make sure that sufficient air flow is provided for the device avoiding to place raceways or other objects which could obstruct the ventilation slits Moreover it is suggested to avoid that devices are mounted above appliances generating heat their ideal place should be in the lower part of the panel Install the device in a place without vib...

Reviews: