CONFIGURATION BY PC
By software DATESOFT it is possible to:
- set the default programming of the device;
- program the options not available with the dip-switch;
(burn-out level, etc...);
- read, in real time, the input and output measures;
- follow the dip-switches configuration wizard.
To configure the device follow the next steps:
1) Power-on the device.
2) Open the protection plastic label on the front of the device.
3) Connect the interface PRODAT to the PC (COM port)
and to the device (PGRM connector).
4) Open DATESOFT.
5) Select the COM port in use.
6) Click on “Open COM”.
7) Click on “Program”.
8) Set the programming data.
9) Click on “Write” to send the programming data to the device.
Warning: during these operations the device must always be powered and the TX/RX cable always connected.
For information about DATESOFT refer to the software's user guide.
DIP-SWITCH CONFIGURATION TABLES
PROGRAMMING
J
1
TX/RX CABLE
PRODAT
COM PORT
P.C.
V+ V-
Q
R
PGRM
Plastic label protection
DAT
POWER SUPPLY
UNIT
1) Open the suitable door on the side of the device.
2) Set the input type by the dip-switch SW1 [1..4] (see TAB.1)
3) Set the minimum input scale value (Zero) by the dip-switch SW1 [5..8] (see TAB.3)
4) Set the maximum input value (Full scale) by the dip-switch SW2 [1..6] (see TAB.3)
5) Set the output type by the dip-switch SW2 [7..8] (see TAB.2)
NOTE:
- It is also possible to set the dip-switches using the wizard of the configuration software following the procedure described in the section ”Configuration by
PC” until the step 6 and clicking on “Switch”.
CONFIGURATION BY DIP-SWITCHES
8
7
6
5
4
3
2
1
8
7
6
5
4
3
2
1
SW1
SW2
Input type
Output
Full scale
Zero
OFF
ON
NOTES:
* To configure the range for the input type selected (TAB.1) refer to the section
of the TAB.3 on next page relative to it (ex: for Potentiometer use the table
TAB.3b ).
* If the dip-switches SW1 [1..4] are all set in the position 0 (“EPROM”), the
device will follow the configuration programmed by PC ( input type and range,
output type and range and options).
* If the dip-switches SW1 [5..8] are all set in the position 0 (“Default”), the
device will follow the input scale programmed by PC for the input type
selected by the dip-switches SW1 [1..4]
* Eventual wrong dip-switches settings will be signalled by the blinking of the
led “PWR”.
0-20 mA
SW2
8
7
TAB.2
Output type settings
4-20 mA
0-10 V
0-5 V
TAB.1
Input type settings
- Input type KTY84-130
- Zero value
0 °C
- Full scale value
200 °C
- Output type
4-20 mA
Ex of configuration:
SW1 =
SW2 =
SW1
3
2
1
EPROM *
4
Pot
KTY81-210
KTY81-220
KTY84-130
KTY84-150
Coster 10K
Coster 1K