CONFIGURATION BY PC

By software DATESOFT it is possible to:
- set the default programming of the device;
- program the options not available with the dip-switch;
  (burn-out level, etc...);
- read, in real time, the input and output measures;
- follow the dip-switches configuration wizard.

To configure the device follow the next steps:
1) Power-on the device.
2) Open the protection plastic label on the front of the device. 
3) Connect the interface PRODAT to the PC (COM port)
    and to the device (PGRM connector).
4) Open DATESOFT.
5) Select the COM port in use.
6) Click on “Open COM”.
7) Click on “Program”.
8) Set the programming data.
9) Click on “Write” to send the programming data to the device.

Warning: during these operations the device must always be powered and the TX/RX cable always connected.
For information about DATESOFT refer to the software's user guide.

DIP-SWITCH CONFIGURATION TABLES

PROGRAMMING

J

1

TX/RX CABLE

PRODAT

COM PORT

P.C.

V+ V-

Q

R

PGRM

Plastic label protection

DAT

POWER SUPPLY

UNIT

1) Open the suitable door on the side of the device. 

2) Set the input type by the dip-switch SW1 [1..4] (see TAB.1)

3) Set the minimum input scale value (Zero)  by the dip-switch SW1 [5..8] (see TAB.3)

4) Set the maximum input value (Full scale) by the dip-switch SW2 [1..6] (see TAB.3)

5) Set the output type by the dip-switch SW2 [7..8] (see TAB.2)

NOTE:
- It is also possible to set the dip-switches using the wizard of the configuration software following the procedure described in the section ”Configuration by 
PC” until the step 6 and clicking on “Switch”.

CONFIGURATION BY DIP-SWITCHES

8

7

6

5

4

3

2

1

8

7

6

5

4

3

2

1

SW1

SW2

 Input type

Output

Full scale

Zero

OFF

ON

NOTES:

* To configure the range for the input type selected (TAB.1) refer to the section 

of  the  TAB.3 on next page  relative to it (ex:  for  Potentiometer  use  the table 
TAB.3b ).

*  If the dip-switches SW1 [1..4] are  all  set in the   position 0 (“EPROM”),  the 

device will follow the configuration programmed by PC ( input type and range, 
output type and range and options).

*  If  the  dip-switches  SW1  [5..8]  are  all  set  in  the    position  0  (“Default”),  the 

device  will  follow  the  input  scale  programmed  by  PC  for  the  input  type 
selected by the dip-switches SW1 [1..4]

*  Eventual wrong  dip-switches  settings  will  be signalled by the blinking of  the 

led “PWR”.

0-20 mA

SW2

8

7

TAB.2
Output type settings

4-20 mA

0-10 V

0-5 V

TAB.1
Input type settings

- Input type              KTY84-130
- Zero value

0 °C

- Full scale value 

200 °C

- Output type 

4-20 mA

Ex of configuration:

SW1 =

SW2 =

SW1

3

2

1

EPROM *

4

Pot

KTY81-210

KTY81-220
KTY84-130

KTY84-150

Coster 10K

Coster 1K

Summary of Contents for DAT 4532 C

Page 1: ...STRUCTIONS The converter must be powered by a direct voltage applied to the terminals Q and R The channel A measures the value from the sensor connected to the terminals I L and G and transmits the output measure on the terminals N and M The channel B measures the value from the sensor connected to the terminals E F and H and transmits the output measure on the terminals P and O The input and outp...

Page 2: ...B 3 4 Set the maximum input value Full scale by the dip switch SW2 1 6 see TAB 3 5 Set the output type by the dip switch SW2 7 8 see TAB 2 NOTE It is also possible to set the dip switches using the wizard of the configuration software following the procedure described in the section Configuration by PC until the step 6 and clicking on Switch CONFIGURATION BY DIP SWITCHES 8 7 6 5 4 3 2 1 8 7 6 5 4 ...

Page 3: ...1 380 390 400 C 5 6 425 450 475 500 525 550 600 800 850 50 100 200 360 650 700 750 370 210 TAB 3a Settings for PTC NTC Zero SW1 8 7 6 5 Default 0 15 30 35 40 45 50 55 60 65 70 75 80 Full scale SW2 4 3 2 1 Default 5 6 8 10 12 14 16 18 20 22 24 26 28 30 32 5 6 SW2 4 3 2 1 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 5 6 SW2 4 3 2 1 68 70 72 74 76 78 80 82 84 86 88 90 92 94 5 6 SW2 4 3 2 1 100 100 10...

Page 4: ...high power supply value 27 Vdc Use of output current Make sure that sufficient air flow is provided for the device avoiding to place raceways or other objects which could obstruct the ventilation slits Moreover it is suggested to avoid that devices are mounted above appliances generating heat their ideal place should be in the lower part of the panel Install the device in a place without vibration...

Reviews: