background image

 Via monte Nero, 40/B – 21049 TRADATE (VA) ITALY 
 Phone: +39 (0)331841070 Fax:+39 (0)331841950 - e-mail:

[email protected]

 - 

www.datexel.it

 

 

DAT 4532 C

DAT 4532 C

Isolated, double channel

converter  for PTC/NTC/Pot 

configurable by Dip-Switch or PC

FEATURES
- Configurable input for PTC, NTC and Pot.
- Configurable output in current or voltage
- Double channel in the same enclosure
- Configurable by dip-switch or PC
- High accuracy
- On-field reconfigurable
- Galvanic isolation among the ways
- EMC compliant – CE mark
- Suitable for DIN rail mounting in compliance       
  with EN-50022 and EN-50035

GENERAL DESCRIPTION

The isolated double channel  converter DAT 4532 C is able to measure and linearise the standard PTC and NTC sensors and potentiometers. In function 
of programming, the measured values are converted in a current or voltage signal. The device guarantees high accuracy and performances stability  both 
versus time and temperature.
The double channel allows the high density mounting where is necessary to reduce the encumbrances.
The programming is made by the dip-switch located in the window on the side of the enclosure. By means of dip-switches it is possible to select the input 
type and range and the output type without recalibrate the device.
Moreover, by Personal Computer the user can program all of the device's parameters for his own necessity;  the configuration by PC allows to program 
the two channels with two independent settings.
Moreover it is available the option of alarm for signal interruption (burn-out) that allows to set the output value as high or low out of scale .
The 1500 Vac galvanic isolation on all ways (inputs, outputs and power supply) eliminates the effects of all ground loops eventually existing and allows 
the use of the converter in heavy environmental conditions found in industrial applications.
The DAT 4532 C is in compliance with the Directive 2004/108/EC on the Electromagnetic Compatibility.
It is housed in a plastic enclosure of 12.5 mm thickness suitable for DIN rail mounting in compliance with EN-50022 and EN-50035 standards.

USER INSTRUCTIONS

The converter must be powered by a direct voltage applied to the terminals Q and R.
The channel A measures the value from the sensor connected to the terminals I, L and G and transmits the output measure on the terminals N and M.
The channel B measures the value from the sensor connected to the terminals E, F and H and transmits the output measure on the terminals P and O.
The input and output connections must be made as shown in the section "Connections".  
It is possible to configure the converter on field by dip-switch or Personal Computer as shown in the section “ Programming ". The configuration by
 dip-switches can be made also if the device is powered (note: after the configuration the device takes some seconds to provide the right output measure ).

TECHNICAL SPECIFICATIONS (Typical at 25 °C and in nominal conditions)

Sensor excitation current

PTC, NTC

500 uA

Linearity 

(1)

PTC, NTC               ± 0.1 % f.s. 

Thermal drift 

(1)

Full scale 

± 0.01% / °C

TEMPERATURE AND HUMIDITY

Operative temperature

-20°C .. +60°C

Storage temperature              -40°C.. +85°C
Humidity (not condensed)

0 .. 90 %

Output type

 

Min

  Max

Min Span 

HOUSING

Material                Self-extinguishing plastic
Mounting                DIN rail in compliance 

with EN-50022 and 

                               EN-50035 
Weight

about 90 g.

Output calibration

Current

± 7 uA

Voltage

± 5 mV

Power supply voltage

18 .. 30 Vdc

Reverse polarity protection

60 Vdc max

EMC ( for industrial environments )

Immunity                 

EN 61000-6-2

Emission                 

EN 61000-6-4

Current consumption 

Current output

55 mA max.

Voltage output

25 mA max.

Burn-out values

Max. output value    

22 mA or 10.6 V

Min. output value    

 0 mA or -0.6 V

Current

 0 mA

20 mA

  4 mA

Voltage 

 0  V

10  V

  1  V

(1)referred to the input Span (difference between  max. and min.)

Response time 

(10÷ 90%) 

about 

 

500 ms

Output load Resistance - Rload

 

Current output

< 500 

Voltage output

> 10 K

Short circuit current                26 mA max.

ISOLATION

Among all ways

         

1500 Vac,
50 Hz, 1 min

POWER SUPPLY

INPUT (2 channels)

OUTPUT(2 channels) 

Input Calibration 

(1)

PTC, NTC            the higher of ±0.1% and  ±0.2°C
Potentiometer      ± 0.05 % f.s. 

Input type

  Min

  Max

Min.Span 

PTC

KTY81-210

-55°C

150°C

 50°C

KTY81-220

-55°C

150°C

 50°C

KTY84-130

-40°C

300°C

 50°C

KTY84-150

-40°C

300°C

 50°C

Pot.

 

(Rnom.< 50K

)

   

%

100 

%

  

10 

%

NTC

Coster 10K

-10°C

100°C

 50°C

Coster 1K

-30°C

  40°C

 25°C

NTC
PTC Pot

V

mA

V

mA

DC SUPPLY

INPUT A

OUTPUT A

+

-

INPUT B

OUTPUT B

NTC
PTC Pot

Summary of Contents for DAT 4532 C

Page 1: ...STRUCTIONS The converter must be powered by a direct voltage applied to the terminals Q and R The channel A measures the value from the sensor connected to the terminals I L and G and transmits the output measure on the terminals N and M The channel B measures the value from the sensor connected to the terminals E F and H and transmits the output measure on the terminals P and O The input and outp...

Page 2: ...B 3 4 Set the maximum input value Full scale by the dip switch SW2 1 6 see TAB 3 5 Set the output type by the dip switch SW2 7 8 see TAB 2 NOTE It is also possible to set the dip switches using the wizard of the configuration software following the procedure described in the section Configuration by PC until the step 6 and clicking on Switch CONFIGURATION BY DIP SWITCHES 8 7 6 5 4 3 2 1 8 7 6 5 4 ...

Page 3: ...1 380 390 400 C 5 6 425 450 475 500 525 550 600 800 850 50 100 200 360 650 700 750 370 210 TAB 3a Settings for PTC NTC Zero SW1 8 7 6 5 Default 0 15 30 35 40 45 50 55 60 65 70 75 80 Full scale SW2 4 3 2 1 Default 5 6 8 10 12 14 16 18 20 22 24 26 28 30 32 5 6 SW2 4 3 2 1 34 36 38 40 42 44 46 48 50 52 54 56 58 60 62 5 6 SW2 4 3 2 1 68 70 72 74 76 78 80 82 84 86 88 90 92 94 5 6 SW2 4 3 2 1 100 100 10...

Page 4: ...high power supply value 27 Vdc Use of output current Make sure that sufficient air flow is provided for the device avoiding to place raceways or other objects which could obstruct the ventilation slits Moreover it is suggested to avoid that devices are mounted above appliances generating heat their ideal place should be in the lower part of the panel Install the device in a place without vibration...