Datel DMS-40PC-4/20S Series Manual Download Page 3

DATEL, Inc., Mansfield, MA 02048 (USA)   

·

   Tel: (508)339-3000, (800)233-2765  Fax: (508)339-6356 

  ·

   E-mail: [email protected] 

 ·

  Internet: www.datel.com

3

4 ½   D I G I T ,   4 - 2 0 m A   I N P U T ,   L E D   D I S P L A Y   M E T E R S

DMS-40PC-4/20S

The following procedure must be performed as the first re-calibration step
every time DIP switches S1 and S2 are changed to select a new display
range. The following procedure also assumes the DMS-40PC-4/20S is
initially completely mis-adjusted, i.e., both potentiometers and both DIP
switches S1 and S2 are randomly set. When performing switch settings,
make sure that the DIP switch's  small actuator is pushed up as far as it
will go to ensure that the switch is truly set to the ON (closed) position.

1. Set R7 (gain/span adjust) and R3 (zero/offset adjust) fully

clockwise, roughly 20 turns, then using the settings found in the
selected range, place the DIP switches on S1 and S2 to the
appropriate positions for the desired display reading.

2. Apply a precision 4mA input with proper polarity and adjust R3

(top 20-turn potentiometer) until the meter's display reads "0000".

3. Apply a precision 20mA input and adjust R7 (bottom 20-turn

potentiometer) until the display reads the maximum desired reading.
Repeat steps 2 and 3 to make sure the adjustments did not affect
one another.

Table 1. DIP- Switch Settings

Using the Decimal Point Settings Table as a guide, the DMS-40PC-4/
20S's decimal points can be enabled to suit the user's particular readout
requirements. Place the selected decimal point's DIP switch to the ON
position (up) to illuminate the decimal point. The decimal points are
merely placeholders, that is, they can all be illuminated or all turned off;
they have no affect on the meter's operation and/or display readings.

Switch S2

SW3

SW4

SW5

SW6

DP1

DP2

DP3

DP4

Table 2. Decimal Point Settings

 Switch S1

 Switch S2

Display Reading

SW1

SW2

SW3

SW4

SW5

SW6

SW1

SW2

       4mA         20mA

1.    0000     2250-2500

Off

On

On

On

Off

Off

On

On

2.    0000     2500-2800

Off

On

On

On

Off

Off

Off

On

3.    0000     2800-3200

Off

On

On

On

Off

Off

On

Off

4.    0000     3200-3850

Off

On

On

On

Off

Off

Off

Off

5.    0000     3850-4300

On

Off

On

On

Off

Off

On

On

6.    0000     4300-4900

On

Off

On

On

Off

Off

Off

On

7.    0000     4900-5600

On

Off

On

On

Off

Off

On

Off

8.    0000     5600-6200

On

Off

On

On

Off

Off

Off

Off

9.    0000     6200-6800

Off

Off

On

On

On

Off

On

On

10.  0000     6800-7750

Off

Off

On

On

On

Off

Off

On

11.  0000     7750-8600

On

On

Off

On

On

Off

On

On

12.  0000     8600-9850

On

On

Off

On

On

Off

Off

On

13.  0000     9850-11000

On

On

On

Off

Off

On

On

On

14.  0000    11000-12000

On

On

On

Off

Off

On

Off

On

15.  0000    12000-13000

On

Off

Off

On

Off

On

On

On

16.  0000    13000-14000

On

Off

Off

On

Off

On

Off

On

17.  0000    14000-15300

On

Off

On

Off

On

On

On

On

18.  0000    15300-16300

On

Off

On

Off

On

On

Off

On

19.  0000    16300-17800

Off

Off

On

Off

On

On

On

On

20.  0000    17800-20000

Off

Off

On

Off

On

On

Off

On

Since the DMS-40PC-4/20S uses extremely-stable thin-film chip
resistors, periodic re-calibration is typically required only in environ-
mentally demanding applications where shock, vibration and tempera-
ture extremes may have a detrimental affect on the 20-turn potentiom-
eters.

(4) Input Grounding: Except for the “-I” suffix models which feature

isolated current loop inputs, all other DMS-40PC-4/20S meters are
supplied with their 4-20mA negative-input terminals (TB1-2, “-”)
internally connected to their power supply ground terminal (TB2-2,
“-V”). This single-ended input configuration is compatible with most
grounded-referenced 4-20mA transmitters.

Applications in which the DMS-40PC-4/20S and its associated 4-20mA
transmitter are connected to a common ground and the transmitter
drives two or more loads (for example, the meter is in series with a
PLC) must have the meter connected as the first device in the current
loop, that is, closest to the system ground (see Figure 2). If this
connection scheme is not possible and/or the meter must be connected
in the middle of the current loop, then‘-I’ suffix models must be used to
provide the required isolation between the meter’s current loop input
and the power supply ground (“-V”). See Figures 2, 3, 4, and 5 for
typical loop connections.

O

perating and Setup Instructions

Reviews: