Operating and Setup Instructions

Performance/Functional Specifications

Typical at T

A

 = +25°C,  unless otherwise noted.

DMS-20LCD-4/20

3 ½   D I G I T ,   L C D   D I S P L A Y ,   4 - 2 0 m A   L O O P - P O W E R E D   M E T E R S

The DMS-20LCD-4/20, using any of the DIP-switch settings described above, can
withstand overcurrents, including those resulting from accidental reverse-polarity
connections, up to ±40mA without sustaining any damage.

Because DATEL's DMS-4/20 loop-powered meters employ active circuitry to convert
the loop current into a voltage, the meters' effective series impedance varies in a
manner that maintains the loop voltage drop constant over the full 4-to-20mA current
range. Listed impedance specification applies at 20mA.

When looking up DIP-switch settings in the Tables and the desired display readings
can be achieved with either of two different settings, using the higher setting # will
produce less sensitive offset (R3) and span (R7) adjustments. Please keep in mind
that the DMS-20LCD standard meter (from which the DMS-20LCD-4/20 is derived)
has an accuracy specification of ±2 counts (max.). Thus, it may not always be possible
to obtain the exact desired display reading.

1. Set R7 (full scale span/gain adjust) and R3 (zero/offset adjust) fully

clockwise, roughly 22 turns, and place SW1-SW6 to OFF.

2. Select DIP switch setting #2.

3. Apply a precision 4mA input, with proper polarity, and adjust R3 until

the meter's display reads "000".

4. Apply a precision 20mA input and adjust R7 until the meter's display

reads "1000". Repeat steps 3 and 4 to make sure the adjustments do
not affect one another.

5. Select the appropriate decimal point by setting SW4, SW5 or SW6 to

ON (DP3, DP2 or DP1 respectively).

NOTE: If a display reading other than "000" to "1000" is desired,

refer to DIP–Switch Settings Table 1 for SW1–SW3 settings.

Current Loop Input

Min.

Typ.

Max.

Units

Full Scale Input Range 

+3.8

––

+20.4

mA

Input Impedance 

––

80

100

Voltage Drop 

––

1.8

2.0

Volts

Overcurrent Protection 

––

––

±40

mA

Performance

Sampling Rate

2.5 readings per second

Accuracy (1 minute warm–up)

±0.05%FS ±1 Count

Temperature Drift  (0  to  +60°C)

––

±0.15

±0.3

Cnts/°C

Display

Display Type and Size

  3½ digit LCD, 0.37"/9.4mm

Polarity Indication

"–" for negative readings

Overrange Indication

"–1_ _ _ " for negative inputs

"1_ _ _ " for positive inputs

Physical/Environmental

Operating Temperature

0

––

+60

° C

Storage Temperature

–20

––

+75

° C

Humidity (Non–condensing)

0

––

95

%

Case Material

Polycarbonate

Weight

0.6 ounces (17 grams)

Display Reading

SW1

SW2

SW3

4mA

20mA

1.  000 to 1050-1999

Off

Off

Off

2.  000 to 650-1350

On

Off

Off

3.  000 to 450-800

Off

On

Off

4.  000 to 300-500

Off

Off

On

5.  000 to 200-300

On

On

On

Table 1. DMS-20LCD-4/20S (Unipolar Model)

DIP-Switch Settings

DMS-20LCD-4/20S

Unipolar reading, loop-powered LCD meter

DMS-20LCD-4/20B

Bipolar reading, loop-powered LCD meter

DMS-20LCD-4/20P

Positive reading, loop-powered LCD meter

DMS-BZL3

Bezel assembly

DMS-BZL4

Bezel assembly with sealing gasket

DMS-20-CP

Panel cutout punch

Ordering Information

A panel-mount retaining clip is supplied with each model.

1. Desired display readings are:

4mA ="0.00"
20mA = "6.00"

Use DIP-switch setting #3 in Table 1 and enable decimal point DP2
via SW5.  Apply 4mA and adjust R3 so the display reads "0.00". Apply
20mA and adjust R7 so the display reads "6.00".

2. Desired display readings are:

4mA = "000"
20mA = "800"

Use DIP-switch setting #2 in Table 1. Apply 4mA and adjust R3 so the
display reads "000". Apply 20mA and adjust R7 so the display reads
"800".  For these display readings, no decimal points are used. Set
SW4, SW5 and SW6 to OFF.

3. Desired display readings are:

4mA    = ".000"
12mA  = ".250"

This example is not as straightforward as the previous two. Notice
that 12mA is exactly halfway between 4mA and 20mA. If we assume
that the input could go up to 20mA, the display reading would then
be: 2 x .250 or ".500". From Table 1 we can now select DIP-switch
setting #4 and enable DP1 via SW6. Apply 4mA and adjust R3 so the
display reads ".000". Apply 12mA and adjust R7 so the display
reads ".250".

Examples (DMS-20LCD-4/20S-Unipolar Model)

ON

1

2

3

4

5

6

ON

DMS-20LCD-4/20S (Unipolar Reading Model)

As shipped, the DMS-20LCD-4/20S is factory calibrated to read "000"
for a 4mA input and "1000" for a 20mA input. The following worst-case
procedure assumes the DMS-20LCD-4/20S is completely mis-adjusted, i.e.,
both potentiometers and the DIP switches are randomly set. When performing

1

2

3

4

5

6

ON

1

2

3

4

5

6

ON

Order on-line at www.datel.com

DIP-switch settings, be sure the DIP switch's small actuators are firmly
engaged in their fully-ON or fully-OFF positions.

Summary of Contents for DMS-20LCD-4/20 Series

Page 1: ...nections to the current loop are made via a reliable two position screw type terminal block The DMS 20LCD 4 20 Series subminiature package houses a large 0 37 9 4mm high digits LCD display that can be read in virtually all lighting conditions including direct sunlight An optional bezel assembly featuring screw fasteners and a rubber seal simplifies panel mounting and provides excellent resistance ...

Page 2: ... Cnts C Display Display Type and Size 3 digit LCD 0 37 9 4mm Polarity Indication for negative readings Overrange Indication 1_ _ _ for negative inputs 1_ _ _ for positive inputs Physical Environmental Operating Temperature 0 60 C Storage Temperature 20 75 C Humidity Non condensing 0 95 Case Material Polycarbonate Weight 0 6 ounces 17 grams Display Reading SW1 SW2 SW3 4mA 20mA 1 000 to 1050 1999 Of...

Page 3: ...less sensitive R3 R7 adjustments can be achieved if the higher DIP setting is selected setting 2 in this example Apply 12mA and adjust R3 so the display reads 000 Apply 20mA and adjust R7 so the display reads 650 Apply 4mA and verify that the display reads 650 Repeat adjustment procedure if necessary 1 2 3 4 5 6 ON 1 2 3 4 5 6 ON Display Reading SW1 SW2 SW3 4mA 12mA 20mA 1 600 to 1000 000 600 to 1...

Page 4: ...reviously calculated Apply 4mA and adjust R3 until the display reads 650 Apply 20mA and verify that the display reads 950 2 Desired display readings are 4mA 4 00 20mA 19 99 This example illustrates the DMS 20LCD 4 20P s capability to display higher differential readings than those indicated in Table 3 This example also illustrates how the DMS 20LCD 4 20P can be used to display the output levels of...

Page 5: ... ISO 9001 ISO 9001 R E G I S T E R E D DMS 20LCD 4 20 3 D I G I T L C D D I S P L A Y 4 2 0 m A L O O P P O W E R E D M E T E R S Mechanical Specifications MECHANICAL DIMENSIONS Inches mm TOLERANCES 2 PL DEC 0 02 0 51 3 PL DEC 0 010 0 254 WIRE SIZE 18 to 26 AWG Solid or stranded STRIPPING LENGTH 0 20 5 08mm 2 56 INSERT 0 156 3 96 DEEP FRONT VIEW 1 280 32 51 0 187 4 75 OPTIONAL BEZEL DMS BZL3 and D...

Reviews: