Model MAC-32-OD
Page 4
energized unless one of two events occur; all relay outputs are in relaxed state or the test push-button
has been depressed.
OPTIONS
Modem
Set Enable for modem use, or Disable for direct P.C. connection.
Echo/Control
Set Echo to control MAC-32-OD from P.C., or control for a Dataprobe’s product controlling the
MAC-32-OD.
Fail Safe
Set Enable to have relay outputs normally in the energized state, or Disable to have relay outputs
normally in the relaxed state.
Dip Switch Settings
Options & Baud Rate Dip Switch (S4)
Position
Description
Open
Closed
2
Modem
Disabled
Enable
3
Echo/Control
Control
Echo
4
Fail Safe
Enable
Disable
5
Reserved
MUST BE OPEN
6
Baud Rate Setting
See Chart Below
See Chart Below
7
Baud Rate Setting
See Chart Below
See Chart Below
8
Baud Rate Setting
See Chart Below
See Chart Below
Baud Rate Settings (S4)
Baud Rate
Position 8
Position 7
Position 6
9600
Open
Open
Open
4800
Open
Open
Closed
2400
Open
Closed
Open
1200
Open
Closed
Closed
600
Closed
Open
Open
300
Closed
Open
Closed
Items shown in
Bold Italic
are the factory default settings.
TEST PUSH BUTTON
The test push button is located on the front panel. The test push button has the following three
functions:
1.
Mute:
Pressing the button less than 2 seconds causes the spare relay to de-energize.
2.
LEDs/Output Test:
Pressing the button more than 2 seconds causes all the relay outputs to
energize and LEDs to light.
3.
Communication test:
Double clicking the button will cause the communication link to be tested. If
test pass, all the LEDs of the MAC-32-OD will flash three times. If test fails, only LED 1 flashes
three times.